Yes as long as you use the correct size breaker.
When you talk about a 220 volt wire and 110 volt wire, the reference is to the insulation factor of the wire. The amount of amperage that the wire has a capacity to carry is independent to the amount of voltage that can be imposed on the wire. When you see wire with ratings of 300 volts, 600 volts and 1000 volts, these are the highest allowable voltages that can be impressed without going over the manufacturers recommendation of allowable voltages. A wire that is rated for 300 volts indicates that the wire is rated for 120 volts or 240 volts or 277 volts. At test research facilities, equipment is tested to destruction. The maximum voltage rating, that is given to the wire as a result of these tests, is the highest safest voltages that can be applied to that particular type of insulation material. So if you hear an electrician say a wire is good for 110 or 220 volts, what is meant is that the same wire can be used for either 110 or 220 volts. To answer the question, you don't need to change a 220 volt wire to a 110 volt wire because it is good for both voltages.
A single phase meter will have two "hot" wires, one black the other red. Each wire will carry 120 volts. Essentially these two wires together will provide you with 240 volts. Hire a professional when dealing with electricity.
10 AWG in copper.
If you combine two 110 volt power lines it does not give you 220 volts, the voltage will be the same. The only way to turn 110 volts into 220 volts is with a step-up transformer.
There are zero amps in 220 wire. When you talk of 220 wire you are making reference to the insulation factor of the wire. Wire in North America is rated for insulation in increments of 300, 600 and 1000 volts. For special applications 5000 volts still has insulation on it. Then there is 7500 volt cable that is classified as concentric neutral cable which is used mostly for underground primary installations. Any voltages higher than that is bare wire. For high voltage installations it is called ACSR. Aluminium Conductor Steel Reinforced. This type of cable uses a steel center support wire and the aluminium conductors are wound around the steel to carry the amperage. This combination of steel and aluminium allow the wire to be spaced over long distances between poles or towers. The amperage classification of wire is based on the circular diameter of the wire. The larger the diameter of the wire the higher the amperage capacity. Three equations to find amps when two factors are known are; Amps = Watts/Volts, Amps = Volts/Resistance and Amps = the sq. root of Watts/Resistance.
Standard wiring for 220 volts which is also referred to as 240 volts, commonly has four wires. One is red, one is black, one is white and one is a bare copper wire. The red and black wire carry 120 volts each, the white wire in usually your neutral which hooks up to your ground along with the bare wire.
A three phase panel will not give you 110 and 220 volts. A three phase four wire panel will, but not at these voltages. The nearest voltages will be 120 and 208 volts. The 120 volt is the wye voltage of 208 volts. 208/1.73 = 120 volts. A single phase three wire panel will give you 110 and 220 volts.
When you talk about a 220 volt wire and 110 volt wire, the reference is to the insulation factor of the wire. The amount of amperage that the wire has a capacity to carry is independent to the amount of voltage that can be imposed on the wire. When you see wire with ratings of 300 volts, 600 volts and 1000 volts, these are the highest allowable voltages that can be impressed without going over the manufacturers recommendation of allowable voltages. A wire that is rated for 300 volts indicates that the wire is rated for 120 volts or 240 volts or 277 volts. At test research facilities, equipment is tested to destruction. The maximum voltage rating, that is given to the wire as a result of these tests, is the highest safest voltages that can be applied to that particular type of insulation material. So if you hear an electrician say a wire is good for 110 or 220 volts, what is meant is that the same wire can be used for either 110 or 220 volts. To answer the question, you don't need to change a 220 volt wire to a 110 volt wire because it is good for both voltages.
A single phase meter will have two "hot" wires, one black the other red. Each wire will carry 120 volts. Essentially these two wires together will provide you with 240 volts. Hire a professional when dealing with electricity.
Wire guage is used as a measurement for the ampacity of the wire. # 14 wire is allowed 15 amp to be applied to it. Voltage is governed by the insulation factor of the wire. The three standard insulations are for 300V, 600V and 1000 volts.
You need to know the amperage to size the wire. For 220 V at 20 A you would need 12 AWG. At 220 V at 30 A 10 AWG.
Wire is sized by the amperage that it is allowed to legally carry. To answer this question the amperage that you need at the garage must be stated.
When flexible cords are talked about the ground wire is in the conductor count. A four wire cord will have black, red, white, and green coloured wires in the flexible cable set. A three wire cord will have a black, white and green coloured wires in the cable set. To use a four wire cord to carry 220 volts just use the black, red and green wires. Connect to the cord ends. Black and red to the outside blade terminal screws and the green wire to the green ground screw. To use a three wire cord to carry 220 volts just use all of the wires. Black and white to the outside blade terminal screws and the green wire to the green ground screw.
With a voltmeter Keep volt meter terminal on phase and neutral wire and it will show the exact volatage
14 gauge wire is for 15 amp circuits. At 220 volts that would be enough for 2.4 kw.At 120 volts it would need 12 gauge wire which is rated for 20 amps.
Use AWG # 3 copper.
10 AWG in copper.