Best Answer

No, in any distribution panel there are individual bars for each termination. The ground buss is in direct contact with the metal enclosure. The neutral is isolated from the metal enclosure. The only place where the two come into contact with each other is where a bonding screw protrudes through the neutral bar and into the metal enclosure.

No, most panels have the option of bonding the neutral as well as the ground bar and the panel enclosure (bonding screw) The bonding screw should never be the only connection to the neutral. The NEC requires that the ground bar be connected to the neutral only at the first panel where utility power is supplied. Every other sub panel downstream must have the neutral and ground separated and the ground bar should always have the bonding screw connecting the enclosure to its respective ground bar. So if the panel is a sub panel, ground and neutral must be separated. The main panel does not. There are other grounding rules related to water pipes and other utilities as well as where the ground rods are driven and bonded. Be sure you understand the rules before attempting a wiring change.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

14y ago

The bus bars in an electrical distribution panel are not replaceable. If you find that some of the bars are corroded or burnt away the best thing to do is replace the whole panel. This is for safety's sake as most electrical fires start with bad high resistance connections that can overheat into combustion.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

in a sub panel no in a main panel they can

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can ground and neutral wires go to same busbar in panel?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

Where are neutral and ground wires usually bonded together?

Only in the main electric panel.


In the typical home electrical panel installation the main ground wire is connected directly from a ground rod driven into the ground to the?

In North American residential homes, there are 3 wires coming from the utility company, two "hots" and neutral. The two "hot" conductors get connected to the main breaker. The neutral gets connected to the neutral bus bars located along the sides of the breaker box. There is a set screw that is placed in the neutral bar that screws into the distribution panel enclosure thereby bringing the potential of the neutral bars down to zero. The wire from your ground rod is also connected to the neutral bus bar, and thereby it is connected to the neutral from the power company. This is also often bonded to the copper cold water plumbing in the house if the home is not plumbed in PVC water pipe. White circuit wires are then connected to the neutral bus bars. Also in the distribution panel are ground bus bars. The ground wires from circuit cables are connected to these grounding bars. Do not under any circumstance terminate the white and bare ground wires together. Ground wires to the ground bar and white wires to the neutral bar.


Where is the only place the neutral and ground wires can be on the same buss bar?

The main electric panel is where neutral is bonded to ground. There is usually a screw or strap that connects the two so the same type panel could be used as a subpanel and have the neutral and ground unbonded in subpanel.


Can you pigtail grounds in a panel in order to prevent double lugging on the neutral bus.?

The ground wires should not be terminated on the neutral bus. They should be terminated on to the ground bus which should be located on the back wall of the distribution panel. The wires don't have to be pigtailed when inserted into the ground bus. More that one wire can go under the terminal screws if you are running out of room. Shut the panel off and remove any ground wires that are now under the neutral bus terminals and move them to the ground bus. Some panels use a lug for a ground bus. All ground wires into the lug and tighten. In a ground fault condition it is the ground wires that are connected to the ground potential that trip the breaker, not ground wires connected to neutrals. Be safe.


Can neutral and bare copper wires be under the same screw on a bus bare in a single family home electrical panel?

No, ground wires should not be terminated on the neutral bus. They should be terminated on to the ground bus which should be located on the back wall of the distribution panel. More that one wire can go under the terminal screws if you are running out of room. Shut the panel off and remove any ground wires that are now under the neutral bus terminals and move them to the ground bus. Some panels use a lug for a ground bus. All ground wires into the lug and tighten. In a ground fault condition it is the ground wires that are connected to the ground potential that trip the breaker, not ground wires connected to neutrals. Be safe.

Related questions

Where are neutral and ground wires usually bonded together?

Only in the main electric panel.


In the typical home electrical panel installation the main ground wire is connected directly from a ground rod driven into the ground to the?

In North American residential homes, there are 3 wires coming from the utility company, two "hots" and neutral. The two "hot" conductors get connected to the main breaker. The neutral gets connected to the neutral bus bars located along the sides of the breaker box. There is a set screw that is placed in the neutral bar that screws into the distribution panel enclosure thereby bringing the potential of the neutral bars down to zero. The wire from your ground rod is also connected to the neutral bus bar, and thereby it is connected to the neutral from the power company. This is also often bonded to the copper cold water plumbing in the house if the home is not plumbed in PVC water pipe. White circuit wires are then connected to the neutral bus bars. Also in the distribution panel are ground bus bars. The ground wires from circuit cables are connected to these grounding bars. Do not under any circumstance terminate the white and bare ground wires together. Ground wires to the ground bar and white wires to the neutral bar.


Where is the only place the neutral and ground wires can be on the same buss bar?

The main electric panel is where neutral is bonded to ground. There is usually a screw or strap that connects the two so the same type panel could be used as a subpanel and have the neutral and ground unbonded in subpanel.


Can you pigtail grounds in a panel in order to prevent double lugging on the neutral bus.?

The ground wires should not be terminated on the neutral bus. They should be terminated on to the ground bus which should be located on the back wall of the distribution panel. The wires don't have to be pigtailed when inserted into the ground bus. More that one wire can go under the terminal screws if you are running out of room. Shut the panel off and remove any ground wires that are now under the neutral bus terminals and move them to the ground bus. Some panels use a lug for a ground bus. All ground wires into the lug and tighten. In a ground fault condition it is the ground wires that are connected to the ground potential that trip the breaker, not ground wires connected to neutrals. Be safe.


Can neutral and bare copper wires be under the same screw on a bus bare in a single family home electrical panel?

No, ground wires should not be terminated on the neutral bus. They should be terminated on to the ground bus which should be located on the back wall of the distribution panel. More that one wire can go under the terminal screws if you are running out of room. Shut the panel off and remove any ground wires that are now under the neutral bus terminals and move them to the ground bus. Some panels use a lug for a ground bus. All ground wires into the lug and tighten. In a ground fault condition it is the ground wires that are connected to the ground potential that trip the breaker, not ground wires connected to neutrals. Be safe.


How many wires meter to breaker panel?

4 wires. 2 hot legs, 1 neutral leg, and 1 ground wire.


In typical home electrical panel installation the main ground wire is connected directly from a ground rod driven into the ground to the?

In North American residential homes, there are 3 wires coming from the utility company, two "hots" and neutral. The two "hot" conductors get connected to the main breaker. The neutral gets connected to the neutral bus bars located along the sides of the breaker box. There is a set screw that is placed in the neutral bar that screws into the distribution panel enclosure thereby bringing the potential of the neutral bars down to zero. The wire from your ground rod is also connected to the neutral bus bar, and thereby it is connected to the neutral from the power company. This is also often bonded to the copper cold water Plumbing in the house if the home is not plumbed in PVC water pipe. White circuit wires are then connected to the neutral bus bars. Also in the distribution panel are ground bus bars. The ground wires from circuit cables are connected to these grounding bars. Do not under any circumstance terminate the white and bare ground wires together. Ground wires to the ground bar and white wires to the neutral bar.


What does neutral do?

Neutral wires are actually ground wires. They enable the circuit to be completed.


How do you connect a 240 v cooktop with 4 wires to a service panel with 3 wires?

The new cooktop has a 4 wire connection. Red & Black are hot. White is neutral, and green is ground. You existing panel is wired with 3 wires. Black & Red are hot and green is ground. There is no neutral wire. Connect the black to black, red to red, and then connect the white and ground together at the plug.


Does the common and ground wires hookup together on main box?

Yes, just at the main panel and not subpanels. The bonding of ground to neutral may be a screw or strap.


What is the difference between a neutral busbar and an earth busbar?

The neutral busbar is the common return path for all of the hot legs. As such, there is current flowing through neutral. If the various hot loads were balanced, effective current in neutral could be zero but, in practice, true balance is hard to maintain.The grounding busbar is the earth protective ground, used to ensure that any fault within a device is shunted to ground, causing the protective device to trip. This prevents the case of the device from becoming hot and causing an electrocution hazard.While neutral and ground are connected together at various points starting at the distribution panel and proceeding towards utility power, it is essential that no operational current flow on ground - it must flow on neutral. Any other condition represents a ground fault which must be corrected.


Can two circuit share the same common and ground wires?

US NEC: The only place two circuits can share the same neutral (common) and ground wires is at the distribution panel, and that is only because those two conductors are tied together at the distribution panel.