answersLogoWhite

0


Best Answer

yes. But this is not a handyman level project. It is suggested you "Call a pro." What you're looking for is not another "main breaker" but a "sub-panel" that is fed by a "feeder" cable from the main panel. Have your electrician calculate the load you'll need in the out-building, then design and install a new feeder circuit and sub-panel for it.

User Avatar

Wiki User

17y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can you add a second main breaker box to control breakers in the out buildings on a farm?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

Will a 100 amp breaker box work if there are 5 220 amp breakers and 7 110 breakers?

It will if the 100 amp distribution board is a 20 circuit board. Ten spaces for the 240 volt breakers and seven spaces for the 120 volt breakers. There are two types of 100 amp breaker boards, one rated at 100 percent and the other at 80 percent. Depending on what rating on the panel board you are using will govern the maximum amount of current that can be legally drawn from the board. This breaker board rating will also govern the size of the main breaker installed and the wire size to feed the board, either 100 amp wire or 80 amp wire. The second consideration is what are the connected loads to the breakers, with the total of seventeen breakers, the board can only supply as much amperage as the main breaker will allow.


Can you change a 250v 15 amp breaker with a 115v15 amp breaker?

No, it would not be safe because 250v is too high for that breaker. <<>> In North America all household breakers are rated at 120/240 volts. A 250 volt 15 amp breaker would would be a two pole breaker and take up two slots in the distribution panel. This can be pulled out and replaced with two separate 15 amp breakers or one 15 amp breaker and a slot panel filler to cover the second slot.


What does 30 amp mean on the electrical box?

It Means it provides or contains conductors and or Overcurrent Protection (breakers/Fuses) that have the ability of carrying 30 Amperes of Electricity. Amps/Amperes is how much electricity in Volume Flows through a given conductor or breaker every second


Why would a breaker trip after 30 sec with nothing plugged in to the circuit except the tv that is turned off?

First unplug the TV. Some TVs may still draw current when off, but not enough to cause a breaker to trip. However you still want to make sure you don't fry your TV as you troubleshoot. If there is nothing plugged in to any outlet on the branch circuit and there are no light fixtures the problem is a bad breaker or in the wiring. The ideal is to have an electrician troubleshoot since you can kill yourself while messing with the breaker panel if you don't know what you are doing. Turn breaker off, make sure with a meter that the breaker is no longer hot and remove the wire by unscrewing the lug screw. Do the same for another breaker of the same rating. Hook the first wire removed to the second breaker. Turn on the second breaker. If it doesn't trip the problem is first breaker, and you need to replace it. If the second breaker trips it is the wiring. With the second wire and breaker restored to original connection, leave the first wire disconnected. Measure the resistance with a meter of the disconnected first wire to neutral which are where white wires are connected in panel. If you have everything unplugged there should be an open circuit. If not you need to start disconnecting wires in outlets and fixtures on the branch circuit and determine where the short is. Since breaker stays on for 30 seconds it is likely the breaker since a dead short would trip breaker immediately. The exception would be a short that is causing a current to flow that is very close to the rating of the breaker. If the breaker is good then I suspect you have something plugged in you don't know about.


Breaker box is full?

You have two options, one is a complete service change. The average house service these days is 200 amps 42 circuits. The second option is to install a sub panel off the existing service. Depending on how many circuits you need will govern the size the sub panel. Here is where it gets tricky. Two side by side single pole breakers or one two pole breaker will have to be removed from the original service panel and replaced with a new two pole breaker. The size of this breaker will be governed by the total load of the new sub panel. The wire from the new sub panel to the two pole breaker is also governed by the load of the sub panel. As an electrician I would recommend that you not do it yourself but get a qualified electrician to do it for you. He would (should) take a permit out for the job and get it inspected.

Related questions

What is one and half breaker system in electrical lines?

One and half breaker system is an improvement on the double breaker system to effect saving in the number of circuit breakers. For every 2 circuits, 1 spare breaker is provided: Two feeders are fed from two buses via their associated circuit breakers and these two feeders are coupled by a third circuit breaker which is called tie breaker. During failure of any of the two feeder breakers, the power is fed via the breaker of the second feeder and main breaker (tie breaker).


Will a 100 amp breaker box work if there are 5 220 amp breakers and 7 110 breakers?

It will if the 100 amp distribution board is a 20 circuit board. Ten spaces for the 240 volt breakers and seven spaces for the 120 volt breakers. There are two types of 100 amp breaker boards, one rated at 100 percent and the other at 80 percent. Depending on what rating on the panel board you are using will govern the maximum amount of current that can be legally drawn from the board. This breaker board rating will also govern the size of the main breaker installed and the wire size to feed the board, either 100 amp wire or 80 amp wire. The second consideration is what are the connected loads to the breakers, with the total of seventeen breakers, the board can only supply as much amperage as the main breaker will allow.


Can you change a 250v 15 amp breaker with a 115v15 amp breaker?

No, it would not be safe because 250v is too high for that breaker. <<>> In North America all household breakers are rated at 120/240 volts. A 250 volt 15 amp breaker would would be a two pole breaker and take up two slots in the distribution panel. This can be pulled out and replaced with two separate 15 amp breakers or one 15 amp breaker and a slot panel filler to cover the second slot.


Where do you connect the two leads of a shunt trip breaker?

Usually the breaker's shunt trip coil is tied to a corresponding current transformer that is sized to the amperage that is allowed to be passed through the breaker. These types of breakers can also be connected into a distribution monitoring device. If the monitor detects a phase reversal or phase loss or voltage rise or drop the breakers shunt trip coil is remotely energized and isolates equipment down stream from the fault. Shunt trip coil circuits are also used as safety circuits where the situation calls for only one breaker to be energized at a time. If the second breaker is inadvertently closed, this would allow both breakers to be on, the second breaker's auxiliary contacts that are an internally part of that breaker will close the safety circuit and energize the shunt trip in the first breaker to causing it to open. So as you can see the two wires could be part of many wiring configurations depending on what situation calls for.


What makes a circuit breaker go bad?

A circuit breaker can go bad from being tripped too many times. Many people don't understand that the tripping of a circuit breaker indicates a problem that needs to be corrected. They usually just reset the circuit breaker, leading to a very common second (or third, or fourth) trip. Circuit breakers tripping are for the prevention of fire due to excessive heat in the circuit. They're not supposed to be tripped repeatedly. This can wear the breaker out. Believe it or not, I've also seen circuit breakers fail to re-energize after being turned off. I speculate this was actually caused by the breaker never having been cycled (it was a main breaker), and the time elapsed since it was installed. Electrical equipment doesn't last forever. It's the same as anything else.


Types of circuit breakers?

There are several type of circuit breakers now a day we are using these are as follows: 1. M.C.B. (Miniature circuit Breaker) Rating : 1, 2, 4, 6, 10, 16, 20, 25, 32, 63 Amperes 2. M.C.C.B. (Miniature current circuit Breaker) Rating : 10, 16, 20, 25, 32, 63, 100, 200, 250, 400 Amperes. 3. A.C.B. (Air Circuit Breaker) Rating : 400, 800, 1000, 1200, 1500, 1800, 2000 Amperes. 4. A. B. Switch (Air Breaker) used in High tension line. 5. SF6 Breaker (Contact break in the Sf6 medium) used in High tension line.


What does 30 amp mean on the electrical box?

It Means it provides or contains conductors and or Overcurrent Protection (breakers/Fuses) that have the ability of carrying 30 Amperes of Electricity. Amps/Amperes is how much electricity in Volume Flows through a given conductor or breaker every second


Where is main breaker switch?

a circuit breaker trips on overload,if this breaker has tripped many times it may be worn out,if there is a overload happening the breaker is doing it s job keeping you safe.Main breaker needs to be replaced when your meter has been pulled(removed from metersocket)Have a electrician look at it and verify problem, you should not attempt to change out yourself it will be live.......


Why would a breaker trip after 30 sec with nothing plugged in to the circuit except the tv that is turned off?

First unplug the TV. Some TVs may still draw current when off, but not enough to cause a breaker to trip. However you still want to make sure you don't fry your TV as you troubleshoot. If there is nothing plugged in to any outlet on the branch circuit and there are no light fixtures the problem is a bad breaker or in the wiring. The ideal is to have an electrician troubleshoot since you can kill yourself while messing with the breaker panel if you don't know what you are doing. Turn breaker off, make sure with a meter that the breaker is no longer hot and remove the wire by unscrewing the lug screw. Do the same for another breaker of the same rating. Hook the first wire removed to the second breaker. Turn on the second breaker. If it doesn't trip the problem is first breaker, and you need to replace it. If the second breaker trips it is the wiring. With the second wire and breaker restored to original connection, leave the first wire disconnected. Measure the resistance with a meter of the disconnected first wire to neutral which are where white wires are connected in panel. If you have everything unplugged there should be an open circuit. If not you need to start disconnecting wires in outlets and fixtures on the branch circuit and determine where the short is. Since breaker stays on for 30 seconds it is likely the breaker since a dead short would trip breaker immediately. The exception would be a short that is causing a current to flow that is very close to the rating of the breaker. If the breaker is good then I suspect you have something plugged in you don't know about.


Breaker box is full?

You have two options, one is a complete service change. The average house service these days is 200 amps 42 circuits. The second option is to install a sub panel off the existing service. Depending on how many circuits you need will govern the size the sub panel. Here is where it gets tricky. Two side by side single pole breakers or one two pole breaker will have to be removed from the original service panel and replaced with a new two pole breaker. The size of this breaker will be governed by the total load of the new sub panel. The wire from the new sub panel to the two pole breaker is also governed by the load of the sub panel. As an electrician I would recommend that you not do it yourself but get a qualified electrician to do it for you. He would (should) take a permit out for the job and get it inspected.


What buildings in the US have Greek columns?

second bank in the united states


Why do two separate breakers control the same outlets?

The only time 2 beakers are run to one outlet is if the outlet is 240V. The breakers should have handle-ties connected to them to ensure that both breakers trip in the event of an overload. Nope its not 240 either,cause it continues to other outlets the same way.and can plug 110 accesories into them. I have come accross this everywhere. In rooms without a ceiling light, one half of a duplex receptacle is a switched lighting circuit and the other is a always on receptacle.