answersLogoWhite

0


Best Answer

For your protection, yes, it should be inspected

User Avatar

Wiki User

16y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Does a new sub panel need to be inspected?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

How do you connect 200amp from main panel to sub panel to the lug of the min panel to lug of sub panel?

Not exactly sure what your question is and you need to make sure you are in compliance with electrical code for your jurisdiction. But, generally speaking you install a large breaker (let's say 100A 2 pole breaker to power the sub panel) just as you would install any other breaker in the presently used (hot) panel, and the proper sized cable then goes from old to new and terminates on the main lugs of the new panel. Ground and neutral are usually isolated from each other in the sub panel but depends on other factors as to location of the sub panel, etc.


How do you make floating ground in 100 amp sub panel Sub panel 30' from main panel and is grded to 2nd 10' rod wired to 1st 10' rod at the main panel. GFCI bkrs are nuisance tripping in bsmt location?

If the sub panel is in the same building remove the bonding screw that bonds the neutral bar to the panels enclosure. Remove the ground from the second ground rod. The sub panel is grounded by the ground wire from the sub panel's feeder. If the panel is separate from the main building treat the sub panel as a separate service. It will need its own ground rods and ground wire from the rods to the neutral bar of the sub panel. Leave the bonding screw in. There will be no ground wire in the conduit between the two services.


When would you want to upgrade the main electrical panel vs just adding a sub-panel?

Depending on how many breakers you have in your exisiting panel if you only have a old 6 or 8 circuit panel then I would suggest a new panel, In the newer building world where you have a 20 or 30 circuit panel then I would suggest a sub panel.


What gauge wire to use for a sub panel?

That would depend upon how many amps will be used in the sub-panel. For example, a 30-A subpanel would need a minimum of 10 AWG feeder conductors.


What should you do if your 200A breaker panel is full and you need to add three forty amp two pole singal throw breakers?

First you need to determine if addition of the new breakers will exceed the 200A service under normal operating conditions. If so you will need to go to power company and increase service and put in a larger main panel. If you have the capacity for the extra current you can add a sub-panel and add the breakers there as well as the breakers you will remove from main panel to accommodate the sub-panel breaker. Another way depends on what breakers are in current panel. There are some breakers that can be duplexed in the same space as a single breaker.

Related questions

Breaker box is full?

You have two options, one is a complete service change. The average house service these days is 200 amps 42 circuits. The second option is to install a sub panel off the existing service. Depending on how many circuits you need will govern the size the sub panel. Here is where it gets tricky. Two side by side single pole breakers or one two pole breaker will have to be removed from the original service panel and replaced with a new two pole breaker. The size of this breaker will be governed by the total load of the new sub panel. The wire from the new sub panel to the two pole breaker is also governed by the load of the sub panel. As an electrician I would recommend that you not do it yourself but get a qualified electrician to do it for you. He would (should) take a permit out for the job and get it inspected.


How do you connect 200amp from main panel to sub panel to the lug of the min panel to lug of sub panel?

Not exactly sure what your question is and you need to make sure you are in compliance with electrical code for your jurisdiction. But, generally speaking you install a large breaker (let's say 100A 2 pole breaker to power the sub panel) just as you would install any other breaker in the presently used (hot) panel, and the proper sized cable then goes from old to new and terminates on the main lugs of the new panel. Ground and neutral are usually isolated from each other in the sub panel but depends on other factors as to location of the sub panel, etc.


What is the maximum amps for a sub panel?

The size of the sub panel is dependant on the amount of connected loads and the amperage of these loads, or the total load in amps on how many new circuits that you will require.


How do you make floating ground in 100 amp sub panel Sub panel 30' from main panel and is grded to 2nd 10' rod wired to 1st 10' rod at the main panel. GFCI bkrs are nuisance tripping in bsmt location?

If the sub panel is in the same building remove the bonding screw that bonds the neutral bar to the panels enclosure. Remove the ground from the second ground rod. The sub panel is grounded by the ground wire from the sub panel's feeder. If the panel is separate from the main building treat the sub panel as a separate service. It will need its own ground rods and ground wire from the rods to the neutral bar of the sub panel. Leave the bonding screw in. There will be no ground wire in the conduit between the two services.


When would you want to upgrade the main electrical panel vs just adding a sub-panel?

Depending on how many breakers you have in your exisiting panel if you only have a old 6 or 8 circuit panel then I would suggest a new panel, In the newer building world where you have a 20 or 30 circuit panel then I would suggest a sub panel.


I have a Transformer 480 primary 208 secondary feeding 1 200amp mb 42 space panel I need to feed a subpanel 6 ft away I'm thinkin feed through lug at top of bus or at feed through MB suggestions?

The sub-panel need to be fed from the main panel, by way of a circuit breaker connected to one of the breaker locations. Or if your sub-panel has a main breaker installed you can feed from the main panel with a sub-feed lug kit. This looks like a breaker, but is only a point where you can branch off the sub panel.


What gauge wire to use for a sub panel?

That would depend upon how many amps will be used in the sub-panel. For example, a 30-A subpanel would need a minimum of 10 AWG feeder conductors.


Can you feed a 60 amp sub panel from another 60 amp sub panel?

Yes


Can you add a second main breaker box to control breakers in the out buildings on a farm?

yes. But this is not a handyman level project. It is suggested you "Call a pro." What you're looking for is not another "main breaker" but a "sub-panel" that is fed by a "feeder" cable from the main panel. Have your electrician calculate the load you'll need in the out-building, then design and install a new feeder circuit and sub-panel for it.


What should you do if your 200A breaker panel is full and you need to add three forty amp two pole singal throw breakers?

First you need to determine if addition of the new breakers will exceed the 200A service under normal operating conditions. If so you will need to go to power company and increase service and put in a larger main panel. If you have the capacity for the extra current you can add a sub-panel and add the breakers there as well as the breakers you will remove from main panel to accommodate the sub-panel breaker. Another way depends on what breakers are in current panel. There are some breakers that can be duplexed in the same space as a single breaker.


Can you feed a 200 amp sub panel from a 200 amp panel?

Judging by your question I'm going to take a guess and say you should probably not attempt to do this yourself. Nor do I recommend it. That being said. You can either have your service upgraded to 200amp, and install a 100amp double pole breaker and branch it off into a 100 amp sub panel. You could most likely re-use your old panel for the 100 amp sub panel. Or... You could have your new 200 amp panel installed in a different location and your current panel wired into it for 100 amps.


How do you wire a garage sub panel box from a 100 amp breaker in the house main panel?

you propaly can't sub panel from 100 amp panel. Just not enough amperage to be worth while. i had to up grade t a 200 amp main first and then I was able to take a 60 sub panel from that.