We require to superheat the refrigerant to ensure that no liquid enters in the compressor.So in most of the cases degree of superheat is kept 2 to 3 deg c
-5 something is wrong
4 * pi * r * r15 Fby subcooling20The formula for calculating the area of a circle - is Pi x r x r
how do i calculate CKG?
how do you calculate the circunference of hemisphere?
discharge pressure is high, suction pressure is high superheat is low and subcooling is high.
To calculate subcooling in HVAC, you need to measure the liquid line temperature and pressure. First, convert the pressure into temperature using a temperature-pressure chart. Subtract the liquid line temperature from the converted temperature to calculate the subcooling. Subcooling is important to ensure the liquid refrigerant leaving the condenser is cooler than its saturation point to prevent the formation of flash gas in the metering device.
add
Superheat was created on 2000-01-25.
On smaller residential air conditioners the manufacturer publishes a charging chart that has the outside air temperature and the corresponding suction and liquid pressure measured by a refrigeration manifold set, gauges. If the chart is not available, you can estimate by measuring the suction pressure and then using a pressure temperature chart for your refrigerant and trying to maintain a 35 degree to 40 degree temperature at the condensing unit or compressor. The other measurement on larger units is the subcooling measurement, measure the actual liquid line temperature and compare the liquid pressure using a pressure temperature chart and also checking for bubbles in the liquid line sight glass. On larger systems after the subcooling has been checked then the superheat has to be checked and the thermostatic expansion valve adjusted if necessary. To check the superheat, measure the suction pressure, convert to a temperature and then measure the actual suction line temperature. The difference is the superheat, should be 6 to 20 degrees depending on the system.
Undercharge can cause HIGH superheat. Overcharge can cause LOW superheat. You need some superheat when charged correctly. How much is needed is depending on outdoor air temperature and indoor wet-bulb temperature.
excess superheat in a capillary tube systems means that there is ______ charge
We require to superheat the refrigerant to ensure that no liquid enters in the compressor.So in most of the cases degree of superheat is kept 2 to 3 deg c
One would need to know what refrigerant is being used along with the indoor and outdoor temps at the time the pressures are checked to give you an answer. The pressure readings only give you part of the story. Suction superheat and liquid subcooling give you more info to help you rate the performance as well.
take your gages and put them on the beginning of the evaporator (afte metering device or txv) and look at saturation temp then get your temp at the suction line (before the compressor)
tell me what is mean by super heat
subcooling methods