If by "60 amp box" you mean a 60-amp service panel (circuit breakers or fuses), you would generally get a 60-A panel that has several slots designed to accept a variety of compatible breakers, from 15A to 60A.
If you have a "box" with no breakers, you would need another "subpanel", with wires from the 60A box to the new subpanel, and install one or more 15A breakers in the subpanel. If you don't need more than one breaker, you might also simply use a 15A disconnect panel with a single breaker in it.
If the full load amps rating of the motor on the name plate is exactly 15 amps you need to use # 12 wire. If it is a longer run you may have to go up one more wire size. The breaker size you need is 30 amps.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
No tandem breakers are of the same value.
A 225 amp load will physically not be able to tie into a 15 amp breaker and a duplex receptacle as you can not get a 3/0 wire under the breaker and receptacle terminal screws.
A 15 amp circuit breaker will handle this situation very well. The smallest home breaker is rated at 15 amp.
If the full load amps rating of the motor on the name plate is exactly 15 amps you need to use # 12 wire. If it is a longer run you may have to go up one more wire size. The breaker size you need is 30 amps.
Replace the 30 Amp Breaker with a 15 Amp breaker.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
No tandem breakers are of the same value.
15 amp breaker.
A 225 amp load will physically not be able to tie into a 15 amp breaker and a duplex receptacle as you can not get a 3/0 wire under the breaker and receptacle terminal screws.
A 15 amp circuit breaker will handle this situation very well. The smallest home breaker is rated at 15 amp.
No, it would not be safe because 250v is too high for that breaker. <<>> In North America all household breakers are rated at 120/240 volts. A 250 volt 15 amp breaker would would be a two pole breaker and take up two slots in the distribution panel. This can be pulled out and replaced with two separate 15 amp breakers or one 15 amp breaker and a slot panel filler to cover the second slot.
Not unless you change the wiring for that circuit. The breaker protects the wiring and if you install a 40 amp breaker on a 15 amp wire circuit you will have a fire in your home.
A 15 amp breaker will trip at 15 amps at an ambient temperature of 104 degree F. If the ambient temperature is higher the breaker will trip before 15 amps and if the ambient temperature is lower the breaker will trip after 15 amps. I would suspect the circuit is overloaded. But, you can change the breaker and see what happens. Just swap it with another one.