In North America there shall be not more that 12 outlets on any 2 wire branch circuit. Such outlets shall be considered to be rated at not more that 1 amp per outlet. Where the connected load is known, the number of outlets may exceed 12 providing the load current does not exceed 80 % of the rating of the over current device protecting the circuit. ( This is not found in the National Electrical Code)
<><><>
Generally each duplex outlet may count for 180VA. For a 15A circuit = 8 duplex max. For a 20A circuit = 10 max. This is in the Wiring Code, by the way. (This only applies to non-residential applications)
In some states the 3 amp per outlet is still being used. For this case, 6 outlets max. ( What States?)
In dwelling units there is no requirement for a maximum number of outlets on a circuit. The circuit could serve a single room of 500 sq. ft. and serve as many outlets you wanted including the lighting loads. (3 watts per sq. ft X 500 sq. ft.) This is the minimum requirement of the code and not necessarily good wiring practice.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
16 outlets or 80% of the total Amperage of the circuit.
Depends on what the outlets are controlling, size of the wire, and size of the breaker.
6 outlets
1
No more than 13.
7 on a 15 amp circuit and 9 on a 20 amp circuit.
Depends on the size wire used in the circuit. If you wired the circuit with AWG #12 wire on a 20 amp breaker then you can install no more than 12 outlets. If you wired it with AWG #14 wire on a 15 amp breaker then install no more than 9 outlets. This is assuming only outlets are on the circuit and nothing else.
Yes. I know of no limits to how many regular receptacles (outlets) you can "piggy back" onto one GFCI receptacle. However, in commercial and industrial construction there are limits to how many receptacles can be placed on any one circuit. These limits in the United States and according to the NEC are: 10 receptacles on a 15 amp circuit and 13 receptacles on a 20 amp circuit.
If they are on the same circuit you only need 1 neutral wire in the circuit.
Install not more that 10 on a 15 amp circuit. You can install 12 if you install a 20 amp circuit.
its an overload on the circuit breaker the 3 outlets are on.. many times groups of outlets are on different circuit breakers.. even though they are in the same room... especially if some are on a gfi outlet
Up to 12 on a 20 amp circuit. Up to 9 on a 15 amp circuit. But use common sense. If the circuit will be heavily loaded, as in a home office, then do not install that many.