Each hot leg to the neutral wire of the service has the ampacity of 200 amps, that is why 3/0 wire is required. A 3/0 copper wire with an insulation factor of 90 degrees C is rated at 210 amps.
If the mains is a 200 amp two pole breaker each leg can carry up to 200 amps in relationship to the common neutral of the service.
A 350 MCM copper conductor will limit the voltage drop to 3% or less when supplying 200 amps for 650 feet on a 240 volt system.
A #1 copper conductor with an insulation rating of 90 degrees C is rated at 145 amps.
The sizing of conduit systems that wire has to be pulled into is dependant on the physical size of the conductor being drawn into the conduit. The second governing factor is the conductor count of the specific conductor that is needed. A 500 MCM copper conductor with an insulation factor of 90 degrees C is rated at 430 amps. This is where the conductor count is need by the service, as to whether the service is single or three phase. In this specific case, the electrical code will allow both single and three phase installations to use the same size conduit. A maximum total of four 500 MCM conductors can be drawn into a 78 mm diameter conduit.
A conductor used for grounding of the main service should be a single wire. The code book has a table that states the size of ground wire for different service panel amperages.
If the mains is a 200 amp two pole breaker each leg can carry up to 200 amps in relationship to the common neutral of the service.
The maximum amps for residential exterior light have different steps. One is having the service equipment like the main panel, entrance conductors, and meter base also having guidelines and code summary.
A 100 amp residential service requires a size #8 copper wire, it should be insulated in green.
75% of US has Residential Phone Service.
Verizon offers great Residential Phone Service in Boston
It will depend on your area but you can check with Verizon to see if they offer residential service in your area.
1950. Residential deliveries reduced to one a day.
Currently, only about a quarter of U.S. households do not have residential phone service. Many other people maintain residential phone service but rarely use it, though this number is not measured.
No, that is an optional service.
A 350 MCM copper conductor will limit the voltage drop to 3% or less when supplying 200 amps for 650 feet on a 240 volt system.
It is a service that offers the transmit of hard copies of documents, letters, parcels.
you can't