A 30 amp circuit breaker is needed unless the load is a motor circuit, then it has to be sized to 250 percent of the motors full load amps.
For 30A circuit is needed breaker 30*1.25=37.5 --> 40A.
If load is lamp or heater, then use breaker of group A or B.
If load is motor, then use breaker of groupC or D (very hard start) or special safe breaker for motor - with variable amp setpoint.
See related link also.
By code you are only allowed 80% of the rating of a breaker. So 30x80%=24amps.
24 amps is the MAX allowed on a 30 amp breaker. You would need a 40amp breaker for a 30 amp circuit. 40x80%=32. So you would want a double pole 40amp breaker.
It is a safety device used to protect a # 10 wire from being overloaded.
In North America the standard sizes for breakers are 15, 20, 30, and 40 amps. The 15 amp size breaker is used in general circuit wiring. The 20 amp size breaker is used for dedicated appliance receptacles, hot water tank and baseboard heating. The 30 amp size breaker is used for a clothes dryer. The 40 amp size breaker is used for the electric range.
For typical residential house wiring 12 AWG wire is required for a 20 Amp breaker. If you change out the breaker for a 25 A breaker you would have to rewire the circuit with 10 AWG. In that case you could up the breaker to 30 Amps. All outlets and switches should be rated at the same voltage and current as the breaker.
No, 10 gauge wire requires the use of a 30 amp breaker. A 20 amp breaker is only used on 12 gauge wire.
The question is one of protection of conductors (wires). A 30 amp breaker must have a #10 copper conductor or larger for adequate protection. A smaller wire (larger number) such as #12, is not protected by a 30 amp breaker. If the equipment you are powering only requires 20 amps, using a 30 amp breaker and #10 AWG wire is acceptable provided all other elements of the circuit are listed for 30 amp circuits.
You never, ever mix wire sizes within a circuit. However you can wire a 30 amp circuit using AWG # 8/3 wire, although that is overkill and AWG #10 wire is what you would normally use on a 30 amp circuit.
Replace the 30 Amp Breaker with a 15 Amp breaker.
Yes.
In North America the standard sizes for breakers are 15, 20, 30, and 40 amps. The 15 amp size breaker is used in general circuit wiring. The 20 amp size breaker is used for dedicated appliance receptacles, hot water tank and baseboard heating. The 30 amp size breaker is used for a clothes dryer. The 40 amp size breaker is used for the electric range.
No. The breaker must protect the circuit components such as wiring, outlets and switches that are connected to the breaker. Therefore if you have a 30 amp circuit as dictated by its components you need to protect it with a 30 amp or less breaker.
Usually 30 Amp 240 volts, but there will be a spec on the well pump.
circuit breaker fuse
30 amp wired with AWG # 10 wire.
Typical residential electric dryers are on 30 amp circuits, which means 10 gage copper wire. The circuit breaker should match the dryer cord rating, generally 30 amps.
No, you should not install a 30 amp circuit breaker to a machine which normally requires a 20 amp supply. The circuit breaker is protecting the wire to the machine. That wire is likely only rated for 20 amps, (# 12 awg). Therefore, a 30 amp breaker could allow too much current to go through the wiring to the machine and cause the wire to burn down. Replace the 3 phase 20 amp breaker with the same amperage breaker.
Yes. You should use 8 AWG wire from breaker to AC unit.
Not if it's functioning properly. The purpose of a circuit breaker is to shut off power if the circuit exceeds the rated power capacity of the wires. Don't plan to exceed the 30 Amp capacity of your house wiring; the results will be destructive.
For typical residential house wiring 12 AWG wire is required for a 20 Amp breaker. If you change out the breaker for a 25 A breaker you would have to rewire the circuit with 10 AWG. In that case you could up the breaker to 30 Amps. All outlets and switches should be rated at the same voltage and current as the breaker.