In NEC 2005 Article 310.10, Conductors for General Wiring it warns that conductors in close proximity to rooftops may experience a temperature rise of 17C (30F) above ambient. It goes on in detail and is referred to throughout the NEC.
nec-es-sar-y
Necessary has four syllables. Nec-es-sar-y
"A" is an indefinite article as is the word "an" ; "the" is a definite article .
article 7073
Article VIII refers to the eighth article of a specific document or agreement. Without further context, it is not possible to determine the specific meaning of Article VIII. It could vary depending on the document or agreement in question.
Grounding
31010 = 1001101102
No Article 210 in the NEC
Article 250 of the National Electrical Code covers grounding.
NEC Article 110.3 is "Examination, Identification, Installation and Use of Equipment."
2008 National Electrical Code - Table of Contents - Chapter 6 Special Equipment - Article 668 Electrolytic Cells
The article designations may change with the code cycle year. In the 2005 NEC see table 310-16 (allowable ampacities for conductors), also article 240.4(D) (protection of small conductors), also table 210.24 (summary of branch circuit requirements for muti-outlet branch circuits)
nec article 422.11[e]
See NEC Article 392. It depends on the voltage, conductor size and the type of cable tray selected.
The population of NEC is 31.
NEC's population is 2,011.
Nfpa 70 2008 nec 200.7 (c) 2