75000va / 480v = 156.25A 156.25A * 125% = 195.31A I would size the breaker at 200A
30 amp
What size breakers are needed for a 30kva transformer 208 volt feed 600 volt out put
An exact breaker size can not be given because the voltage, and hence the calculation for current, is not given. A transformer shall be protected by an over current device that is not rated at more that 150% of the primary current.
Cable is not rated in kva.
The question isn't the number of amps total on your branch circuits, but rather, what your MAIN breaker(s) are rated at. This will determine what size of generator you will need. And be certain that the generator is 3-phase. <<>> The formula you are looking for is Amps = kva x 1000/1.73 x voltage.
A breaker is not sized by individual phase amperage. It will be a three phase or three pole breaker rated at the output of the generator. Use the following formula to find the output amperage of the three phase generator. Amps = kva x 1000/1.73 x voltage.
A 15 KVA - Generator operating at 380 Volts can cater to only 22.79 Amps. It cannot cater to a 60 Amps breaker
Read the label on the side.
35 sq. mm
At what pressure air is blast in air blast circuit breaker during fault intruption?
You don't calculate the rated kV.A of a circuit breaker; it's determined by the manufacturer. It's important that a circuit breaker's rated kV.A exceeds the fault level kV.A at the point where the circuit breaker is located, otherwise it may fail to interrupt a fault current and, possibly, self destruct.