3000 / 240 = Amps. You de-rate a breaker by 20 % for continuous load like an oven. You could get by with a 20 Amp breaker and 12 AWG wire. However, I would recommend 30 Amps and 10 AWG for an oven for the long run.
To calculate the current the equation is Watts divided by Volts.
3600 / Volts = Amps
The current should be less than or equal to 80% of the Breaker Size. For example a 30 amp breaker should carry no more than 24 amps continuously.
a 30 amp breaker will work. the formula is power divided by voltage and then use next size up
50 amp breaker wired with AWG # 6 wire.
The size breaker you use is determined by the size wire used in the circuit. If you use AWG #12/2 wire then use a 20 amp breaker. If you use AWG # 14/2 then use a 15 amp breaker.
A 15 amp dedicated circuit breaker should be used for the dishwasher. The disposal can be wired to the general kitchen 15 amp circuit.
Depends on how many amps it pulls and the size of the wire in the circuit.
In North America the standard sizes for breakers are 15, 20, 30, and 40 amps. The 15 amp size breaker is used in general circuit wiring. The 20 amp size breaker is used for dedicated appliance receptacles, hot water tank and baseboard heating. The 30 amp size breaker is used for a clothes dryer. The 40 amp size breaker is used for the electric range.
50 amp breaker wired with AWG # 6 wire.
running wire 12-2 300ft w/9ea. 27watt lights what size breaker should be used
The size breaker you use is determined by the size wire used in the circuit. If you use AWG #12/2 wire then use a 20 amp breaker. If you use AWG # 14/2 then use a 15 amp breaker.
30 amp breaker with #10 gauge copper wire
A 15 amp dedicated circuit breaker should be used for the dishwasher. The disposal can be wired to the general kitchen 15 amp circuit.
You use the correct size breaker depending on the size wire in the circuit. If the circuit is wired with AWG #12 wire use a 20 amp breaker. If it is wired with AWG #14 wire then use a 15 amp breaker.
Depends on how many amps it pulls and the size of the wire in the circuit.
In North America the standard sizes for breakers are 15, 20, 30, and 40 amps. The 15 amp size breaker is used in general circuit wiring. The 20 amp size breaker is used for dedicated appliance receptacles, hot water tank and baseboard heating. The 30 amp size breaker is used for a clothes dryer. The 40 amp size breaker is used for the electric range.
The breaker commonly used for ranges is a 40 amp. This size is used to cover the total wattage of the range. If for some reason all of the top elements and the oven were in use at the same time then the amperage drawn would be just under the trip setting of the breaker. If this same scenario were played out on the range with a 30 amp breaker supplying the power it would trip the breaker.
20 amp breaker 12 gauge wire assuming its 120 volt
Use 15 amp breaker with 14 gage wire or 20 amp breaker with 12 gage wire. Either way will work just fine.
The sizing of the circuit breaker and hence the wire size to feed the pump are all dependant upon the amperage of the pump. This question can not be answered without that information.