Hire an electrician. Do not install your main service yourself. It must meet code, it must follow many regulations to the letter, it must be inspected, and it must be done my a licenced professional. You will not save money by trying to do it yourself, and it is illegal. Chances are your power company will not connect service if it is not installed by a licenced professional.
Use 3/0 copper.
<<>>
To over come the voltage drop and maintain a full 200 amps at the load end, a 250 MCM copper conductor will limit the voltage drop to 3% or less when supplying 200 amps for 250 feet on a 240 volt three wire system.
AWG 0000 (4/0)
<<>>
A 250 MCM copper conductor with an insulation factor of 75 or 90 degrees C are rated at 255 and 265 amps respectively.
1 1/4 inches
A #1 copper wire with an insulation rating of 90 degrees C is rated at 140 amps.
Yes, they are the same size wire.
A 200 amp service panel will require a # 4 bare copper ground wire.
On a 200 amp or any size service the ground wire is easily identified. Look in the distribution panel for the neutral bus bar. This is where the service neutral (white wire) is connected to the distribution panel. There you will see a bare copper wire connected to the same neutral bar. This is the ground wire that is connected to the ground rods out side of the house.
You do not use a ground wire in the connection from the meter base to the distribution panel. A bonding wire may be required if the service is using PVC conduit.
A #1 copper wire with an insulation rating of 90 degrees C is rated at 140 amps.
Yes, they are the same size wire.
A 200 amp service panel will require a # 4 bare copper ground wire.
AWG # 3/0 copper.
As a service entrance wire you need AWG # 3/0 gauge copper.
A 200 amp service panel with a 60 amp sub-panel.
On a 200 amp or any size service the ground wire is easily identified. Look in the distribution panel for the neutral bus bar. This is where the service neutral (white wire) is connected to the distribution panel. There you will see a bare copper wire connected to the same neutral bar. This is the ground wire that is connected to the ground rods out side of the house.
You do not use a ground wire in the connection from the meter base to the distribution panel. A bonding wire may be required if the service is using PVC conduit.
200 amp service in chicago uses 3 aught.
Yes, the wire size has to be increased. The existing 100 amp service will now probably have a #3 conductor with an insulation factor of 75 or 90 degrees C which is rated for 100 and 105 amps respectively. Increasing to a 150 amp service will use a #1/0 wire size. If you are thinking of an upgrade, skip the 150 amp service and go to a 200 amp panel. New homes are installing 200 amp 42 circuit panels. The extra cost is only reflected in the materials as the labour costs will be the same regardless whether a 150 amp or a 200 amp panel is installed. The wire size for a 200 amp panel is #3/0. With an insulation factor of 75 or 90 degrees C the rating is 200 or 210 amps respectively.
200 Watt Panel
6