answersLogoWhite

0


Best Answer

It mostly depends on the voltage of the circuit. Watts is the product of amps x volts. Amps = Watts/Volts. 600/120 = 5 amps, 600/240 = 2.5 amps. In both cases a #14 copper R90 degree wire will do the job. It is rated at 15 amps.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

14y ago

4 gauge although i think you could use 8 but i have my 800 watt amp to a 4 gauge so just go with that

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

At least 8 gauge but 4 gauge would be better. Check the size of the B+ and GND holes on your amp. If you can stick your pointer finger in it then it's 4 gauge. If you can't it's 8 gauge.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

For service conductor not exceeding 800 amps, the required copper grounding conductor is 1/0 AWG.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

It depends on where the wire is being used, but for the power supply for an ordinary domestic audio amplifier, wire of 0.75 mmsq is adequate, and need to be protected by a 5-amp fuse.

This answer is:
User Avatar

User Avatar

Wiki User

13y ago

A #14 copper wire will handle 760 watts with some to spare. Load on a #14 wire is 15 amps X .8 = 12 x 120 = 1440 watts.

This answer is:
User Avatar

User Avatar

Wiki User

13y ago

A #4 copper wire with an insulation rating of 75 or 90 degrees C is rated at 85 amps.

This answer is:
User Avatar

User Avatar

Anonymous

Lvl 1
3y ago

2/0 coper

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size ground wire for 800 amp service?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What wire size to use from breaker box to earth ground rod?

The wire size used in a service entrance distribution panel is governed by the size of the services over current device. The larger the service, the larger the fault current could be, the larger the ground wire to carry the fault current to ground. If the largest service conductor carries 100 amps use a #8, 200 amps - #6, 400 amps - #3, 600 amps - #1, 800 amps - 1/0 and over 800 amps - 2/0 for the ground wire. <<>> Golden Valley Electric Assoc. in Alaska requires #4AWG copper wire for a ground from the breaker box to earth ground rod. The same goes from the service entrance panel on the pole.


What size ground wire should you use on a 1200 amp service?

You need to say whether it's a 150 amp service or a 1200 amp service it has to be one or the other. <<>> A 1/0 copper conductor with an insulation factor of 90 degrees C is rated at 155 amps. There is no ground wire stated for a 150 amp service so the next size up is a 200 amp service. The ground wire for this size is #6 bare AWG. Without knowing what types of loads that are coming off of the distribution a reduced neutral can not be recommended. The neutral will be the same size as the service conductor which is 1/0.


What size conductors are needed for 800 amp service?

500


What size ungrounded conductor for 800 amp service?

A 3/0 copper conductor would allow you up to 100 feet at 800 Amps with only 5 percent voltage drop, assuming 240-volt service. If it were a 3-phase 480-volt service, you could go more than 23 feet with only a 5 percent drop. <<>> The size of conductors for an 800 amp service could be sized in several ways. Using a single conductor is out of the question as the size will be impossible to bend or handle. A 2000MCM wire only has a rating of 775 amps. Most high amperage services will use parallel runs to add up to the required amperage. A parallel run of 600 MCM will give you a total of 910 amps. A triple parallel run of 300 MCM will give you a total of 885 amps. A quad parallel run of 3/0 will give you an amperage of 840 amps. The key here is to find the most economical way of installing the service. Take into account the availability of triple barrel or four barrel lugs, wire costs for the larger sizes and the labour to man handle the larger sizes into the main switch. These size services that I have installed, the customer opted for the four barrel lugs with 3/0 wire. The 3/0 wire is a readily available item even though the lugs may have to be a special order.


800 amp service using parallel sets of 500 cu what size grounding electrode conductor?

The size called for is one ought (0). There are addendum to this rule depending on where you live in the country. Check the addendum to this code rule in your area.

Related questions

What wire size to use from breaker box to earth ground rod?

The wire size used in a service entrance distribution panel is governed by the size of the services over current device. The larger the service, the larger the fault current could be, the larger the ground wire to carry the fault current to ground. If the largest service conductor carries 100 amps use a #8, 200 amps - #6, 400 amps - #3, 600 amps - #1, 800 amps - 1/0 and over 800 amps - 2/0 for the ground wire. <<>> Golden Valley Electric Assoc. in Alaska requires #4AWG copper wire for a ground from the breaker box to earth ground rod. The same goes from the service entrance panel on the pole.


What size ground wire should you use on a 1200 amp service?

You need to say whether it's a 150 amp service or a 1200 amp service it has to be one or the other. <<>> A 1/0 copper conductor with an insulation factor of 90 degrees C is rated at 155 amps. There is no ground wire stated for a 150 amp service so the next size up is a 200 amp service. The ground wire for this size is #6 bare AWG. Without knowing what types of loads that are coming off of the distribution a reduced neutral can not be recommended. The neutral will be the same size as the service conductor which is 1/0.


What size conductors are needed for 800 amp service?

500


What wire size for 15000 Volts and 550 amp service?

There are two distinct questions here. To determine the wire size to carry 15000 volts the circuits load amperage must be stated. The wire size for a 550 amp service is, an 800 MCM copper conductor with an insulation factor of 90 degrees C. This conductor is rated at 555 amps. Parallel 250 MCM will give you a total capacity of 580 amps. A triple run of 2/0 will give you a total capacity of 585 amps.


What size wire needed for 50 amp service 800 feet away 120 volt RV Trailer 3600 watts plus a security light or outdoor outlet What size breaker at the supply disconnect receiving panel disconnect?

A 500 MCM copper conductor will limit the voltage drop to 3% or less when supplying 50 amps for 800 feet on a 120 volt system. 500 MCM wire diameter is 1/2 inch. As you can see there will be trouble getting that size wire into a 50 amp breakers lug. On installations like this to offset the voltage drop at such a low voltage, a transformer should be used at both ends. The first transformer to raise the voltage and the second transformer to lower it at the 800 foot end. If you use two 480 volt transformers a #1 wire can be used between them. A #1 copper conductor will limit the voltage drop to 3% or less when supplying 50 amps for 800 feet on a 480 volt system. By increasing the voltage you can see that a smaller wire size can be used. On an installation of this nature, a primary line should be brought to the RV site and a service distribution panel established at that point and any RV vehicles can then be fed from that service.


What size wire is needed for 800 amp service?

Loaded question, what is the voltage, run length, aluminum or copper feeders, expected constant load? Definitely bigger than 4/0


What is Rea Magnet Wire's population?

The population of Rea Magnet Wire is 800.


Gmail customer service ((800))-923-0024 service talk to person is correct number?

customer service ((800))-923-0024


What size ungrounded conductor for 800 amp service?

A 3/0 copper conductor would allow you up to 100 feet at 800 Amps with only 5 percent voltage drop, assuming 240-volt service. If it were a 3-phase 480-volt service, you could go more than 23 feet with only a 5 percent drop. <<>> The size of conductors for an 800 amp service could be sized in several ways. Using a single conductor is out of the question as the size will be impossible to bend or handle. A 2000MCM wire only has a rating of 775 amps. Most high amperage services will use parallel runs to add up to the required amperage. A parallel run of 600 MCM will give you a total of 910 amps. A triple parallel run of 300 MCM will give you a total of 885 amps. A quad parallel run of 3/0 will give you an amperage of 840 amps. The key here is to find the most economical way of installing the service. Take into account the availability of triple barrel or four barrel lugs, wire costs for the larger sizes and the labour to man handle the larger sizes into the main switch. These size services that I have installed, the customer opted for the four barrel lugs with 3/0 wire. The 3/0 wire is a readily available item even though the lugs may have to be a special order.


AOL customer service number ((800))-923-0024 service talk to person is correct number?

customer service ((800))-923-0024


What size wire do you need to connect a camera that's 800' from the power source if it needs 24V AC and it draws 4A and uses 59W?

A gigantic expensive cable run of #8 gauge wire to a 3:1 transformer.


What size ground rods for 800 amp electrical service?

You will need two 8 foot ground rods. One placed under the meter base and another one placed 6 feet to the side next to the foundation. If this is a home I highly recommend you install a 200 amp service instead of a 100 amp service. Not much more expensive and you will have plenty of room for growth.