It is unusual to have multiple outlets on a 30 Amp service. If you do this you need outlets rated at 30 amps and 10 AWG wire.
A 15 amp circuit breaker is used to protect a # 14 copper wire which is the minimum size wire that can be connected to a 15 amp receptacle.
You use the correct size breaker depending on the size wire in the circuit. If the circuit is wired with AWG #12 wire use a 20 amp breaker. If it is wired with AWG #14 wire then use a 15 amp breaker.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
Depends on the size of the wire going to the A/C. If the wire is AWG #10 you cannot install a 40 amp breaker. If the wire is AWG #8 you can.
You need a 60 amp breaker.
The size breaker you use is determined by the size wire used in the circuit. If you use AWG #12/2 wire then use a 20 amp breaker. If you use AWG # 14/2 then use a 15 amp breaker.
A 15 amp circuit breaker is used to protect a # 14 copper wire which is the minimum size wire that can be connected to a 15 amp receptacle.
You use the correct size breaker depending on the size wire in the circuit. If the circuit is wired with AWG #12 wire use a 20 amp breaker. If it is wired with AWG #14 wire then use a 15 amp breaker.
Depends on the wire size you are using. If the generator breaker is a 30 amp then install a 30 amp breaker.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
Depends on the size of the wire going to the A/C. If the wire is AWG #10 you cannot install a 40 amp breaker. If the wire is AWG #8 you can.
You need a 60 amp breaker.
10 AWG.
Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.
Not unless the wire going to the refrigerator outlet is AWG 10/2. If it is wired with 12/2 wire then you must use a 20 amp breaker. Using a 30 amp breaker is dangerous and a fire hazard.
25 amp breaker
Depends on the wire size used in the circuit. If you use AWG # 14 wire you must use a 15 amp breaker. If it is wired with AWG # 12 wire then you use a 20 amp breaker. If a AWG # 10 wire is used then a 30 amp breaker is required. The breaker protects the wiring from overheating so you must use the proper size breaker for the wire used.