Best Answer

4 gauge AWG copper minimum. Use this:
http://www.electrician.com/vd_calculator.html
I found this invaluable when wiring our outbuildings. This one puts out the wire size:
http://www.alternate-energy.net/voltlosscalc03.html

User Avatar

Wiki User

18y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

16y ago

It is illegal for you to do this yourself and the power company won't reinstall your meter if you do. Call an electrician. Because of the danger of a fire for an improperly sized service cable , you should seek the advice of a certified electricion, or your local electric provider or an employee in the electric dept. in a home improvement store.

This answer is:
User Avatar

User Avatar

Wiki User

17y ago

number six wire is good for sixty amps max Added by maintain... First, I am assuming that you are not an electrician. Second, I would suggest that you check with your local building official, it sounds like you may need a permit. Third, #6 THHN conductors will work under optimal conditions. However, there may need to be some deration factors applied. THHN may not work if the conductors are exposed to light, are installed in wet locations or other situations. It is best to check with a qualified electrician or local building official before you invest time and money on a project that will not work the way you want. Best of luck! Terry

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

That is quite a distance for a sub panel. 2/0 Aluminum would be the correct wire size. If for another building, a 100 amp service with it's own meter would be more practical and probably cost less. You would need a meter&pan, main box and service stub for the utility company to connect to. 275 feet of 2/0 service wire is going to cost you several hundred dollars alone. If you plan to get there underground, that is a big expense. Over head, you would need at least 4 support poles. (probably 6--max 50ft between poles for correct support plus strand guy wire to support cable.)

<<>>

A utility company will only allow one 120/240 volt drop to each property. A 4/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 100 amps for 275 feet on a 240 volt system.
A 1/0 copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 275 feet on a 240 volt system.
When connecting a 100 amp sub panel check to see if the panel is 100% rated for 100 amps. Many are only rated for 80% capacity. If this is the case then the wire should be sized for 80 amps.

A #1 copper conductor will limit the voltage drop to 3% or less when supplying 80 amps for 275 feet on a 240 volt system.
RWU90 cable is direct burial but needs protection where it comes out of the ground to the panel. Also in the 100 amp sub panel you would need a #6 copper ground wire, 2 ground rods or a 2'x2' ground plate, buried 3' deep.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

A #3 copper wire insulation rating of 90 degree is rated at 105 amps.

This answer is:
User Avatar

User Avatar

Wiki User

10y ago

#3 copper wire if it is very close by.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

In copper 2/0 (2 Ought)


This answer is:
User Avatar

User Avatar

Wiki User

11y ago

NEC 310.16

#3 Thhn Copper

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What wire gauge for a sub panel 100a sub panel off a 200a sub panel?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What gauge of cooper service wire for 200A service to meter box and service panel?

bed


What size cable is used for house wiring?

Copper SE cable gauge 00 from the meter socket to the breaker panel for a 200A service. Then 8, 10, 12, and 14 gauge wire depending on the load.


What size pipe and size aluminum wire are required for a 100A sub panel off a 200A main service?

A #1 aluminum wire with a insulation factor of 90 degrees C is rated at 105 amps. Three #1 wires can be installed into an 1 1/2" conduit.


Can you 14 gauge wire from the panel box to 12 gauge wire to the light?

no


What is the max amps for a 4 gauge wire can 4 gauge feed a 100A breaker box?

Yes, # 4 AWG copper and 100 amps is the max.


What gauge electrical wire is required to upgrade your electircal service to 200A if your incoming service is underground?

4/0 Aluminum or 2/0 Copper type USE.


Where does ground wire connect to gauge panel on 1981 corvette?

there is no ground in a car electrical system.


What size wire do i ned tor 90f run 125amp sub panel?

Use 1/0 gauge.


Is a 6 gauge 4 conductor wire still used to install a 240V 50A hot tub more than 50 ft away from the panel?

Yes, that is the correct wire gauge. However, if your tub is much more than 100 ft. from the panel you might consider going up in wire size to #4 due to voltage drop.


How big is 6 gauge wire?

The size of the wire is stated by its gauge under American Wire Gauge. Six gauge wire is size 6 AWG.


Is 8 gauge weld wire fencing stronger than 10 gauge wire?

Wire gauges are defined in such a way that the lower the gauge, the thicker the wire. So, 8 gauge wire is thicker than 10 gauge wire.


How many amps can a 8 gauge wire run coming from the ditribution panel to the sub panel 25 feet away?

A #8 copper wire with an insulation factor of 75 or 90 degrees C is rated at 45 amps.