Fuses, Circuit Breakers, GFCI (Ground Fault Circuit Interrupter), Surge Protector, etc.
A GFCI outlet has a TEST and RESET switch. Press reset and see if it fixes problem. If reset won't stay in that means that a ground fault condition is present and may be on another outlet that is fed from the tripped GFCI. If this isn't the problem check the main breaker feeding the GFCI and ensure it isn't tripped. If none of this works the GFCI itself may be bad. If you have a Volt Meter you can remove the outlet from the wall receptacle and make sure there is voltage present. You can also see if there is a branch circuit connected. To troubleshoot you can disconnect the branch circuit and then try reset. If you have voltage on input and GFCI won't reset with branch circuits removed, replace the GFCI.
Not if the GFCI breaker is supplying the circuit you are wanting to put the GFCI receptacle into.
Your question is a bit vague, but let's try a two part answer. If you have a GFCI breaker in an electric panel you should only have one connection at the breaker, but the breaker will protect all devices on the circuit. If you are talking about a GFCI outlet, they are equipped to extend the GFCI protection to other non-GFCI outlets by using the proper "output" connection on the GFCI.
Deoends on code you are governed by. In USA, a GFCI outlet or a circuit controlled by a GFCI circuit breaker would be required.
It is a Ground Fault Circuit Interrupter or GFCI. It can either be equipped in your electric panel as a GFCI breaker, or in a GFCI outlet which also lets you extend the GFCI protection to other outlets "down the line" from the GFCI outlet.
Yes, in the form of GFCI circuit breakers, not as a receptacle.
Ground Fault Circuit Interrupter (GFCI).
In rooms without exposure to water such as a bedroom or living room. Typically, GFCI is used in bathrooms, kitchens, garages, outdoors and sometimes basements.
you need greenhouses/hoop houses and trees, shrubs, perennials
Fuses, Circuit Breakers, GFCI (Ground Fault Circuit Interrupter), Surge Protector, etc.
Yes. You are allowed to use a neutral for one circuit from each phase of your service. For example, in a residential service, you can use the same neutral for circuits 1 and 3. In a commercial (3 phase) service, you can use a neutral for circuits 1, 3, and 5. You will experience problems if you use a neutral for two 'black' circuits or two 'red' circuits, if the circuits originate from the same phase bus bar. Also, AFCI's are sensitive to sharing neutrals, but GFCI's are not.
Unless the motor is used for SPA/pool type use, it does not need a GFCI. Motors can cause nusiance GFCI trips due to sparking at start up. Ideally motors should be operated on dedicated circuits.
A GFCI outlet has a TEST and RESET switch. Press reset and see if it fixes problem. If reset won't stay in that means that a ground fault condition is present and may be on another outlet that is fed from the tripped GFCI. If this isn't the problem check the main breaker feeding the GFCI and ensure it isn't tripped. If none of this works the GFCI itself may be bad. If you have a Volt Meter you can remove the outlet from the wall receptacle and make sure there is voltage present. You can also see if there is a branch circuit connected. To troubleshoot you can disconnect the branch circuit and then try reset. If you have voltage on input and GFCI won't reset with branch circuits removed, replace the GFCI.
A GFCI trips when it detects a difference in the amperage going to the outlet and what is coming back. Even 4-6 miliamps difference will trip the outlet.
Not if the GFCI breaker is supplying the circuit you are wanting to put the GFCI receptacle into.
Yes. In Canada no, the main incoming service is not protected with GFCI's. The code calls for selective branch circuits to be protected. In the new code regulations the GFCI's will be replaced with arc fault protection to monitor the selective circuits.