Want this question answered?
simply put a motor consumes power and a generator produces it. reactance of a generator = - reactance of a motor
No, Power factor may not have a magnitude greater than 1. It represents the proportion of power used by the load as compare to the total power delivered to the load. If the load is able to store power, then some of the power delivered to the load will be stored and then returned back to the electricity supply (50 times a second, depending on your grid frequency).
This will require a modification to your units to allow them to be "hooked" together. You will have to add another connection to your generator that connects to your generator output, one cable for each fase. Connect a slave cable from one unit to the other, and connect the communication cable so they can share the load. The generator will do the rest.
To lift a 950-N load 3 meters requires (950 x 3) = 2,850 joules of energy.The power is the rate at which the energy is delivered. It takes more powerto lift the load faster.The power used to lift this load is (2,850 joules) divided by (the number of seconds it takes),and the unit of the answer is watts.
Electrical engineers use it in calculating power factor and electrical load distribution when dealing with 3 phase power connections.
Load rejection occurs when load is suddenly removed from the generator. The most obvious example of this is the breaker connecting the generator to the power grid opens. This results in a full load rejection. Load pick up means the generator is supplying power to a given load. When a generator comes on line, it will pick up some load that might have been supplied by another generator.
The load on a generator is a general word for whatever device is connected to it to use the power that is being generated.
because the incoming generator has be connected as a source and not a load to the grid. if the frequency of the incoming generator is lower than the grid frequency then ... it will behave as a motor drawing power from the grid and generator will trip in reverse power protection.
A generator, rated at 16 MW, should be able to continuously supply a load of 16 MW. You don't need to compute its 'minimum load', because the minimum load will be zero watts! In other words, you can run the generator with no load whatsoever if you wish to waste fuel.The point is that the power supplied by a generator is determined by the load, NOT by the generator itself -so it is important that the generator is capable of supplying the maximum load applied to it. A generator's 'rated power output' simply tells us the maximum load it is capable of supplying.
The governor controls the speed of the power source rotating the generator. This has to be continually adjusted to match the load on the generator. As more load is switched on, the generator becomes harder to turn, this would cause the generator to slow down, unless the power unit is adjusted to increase power and correct the speed.
Real power output from a generator is determined by whatever is turning the generator shaft. If one generator's prime mover is supplying ~50MW of power, and the other is supply ~50MW, they will share the load equally. If one starts generating more, it will take on more of the load. If the load doesn't change, and one starts to produce more power, the system frequency and voltage will start to increase, effectively increasing the load.
a curve drawn for power against load angle maximum power occurs at load angle of 900 maximum power will be transffered from sending end to receiving end when the reactance is 1.732 times its reactance
When using a resistive load bank to test a generator, it does not matter if you load the generator to its kW or kVA rating, because those two numbers are the same when considering a resistive load. Power factor, which is the difference between true and apparent power, only comes into play when there is a reactive (inductive or capacitative) load.
The 10 A in the load includes the real power and the reactive power, if it is a single phase 120 V generator it can supply 16.67 A; that means a 2000 KW load at a power factor of 1.00, of for example a 1600 W load at a power factor of 0.80, in both cases the output current of the generator will be 16.67 Ampers, it is the same with the 10 A load, the power factor is included in the supplied current.Rosa María Valdespino.
If the 1600 represents 1600 watts like most generator numbers do, then the generator can deliver enough power to run a 1600 watt load connected to it.
simply put a motor consumes power and a generator produces it. reactance of a generator = - reactance of a motor
In an electric generator, the function of a capacitor is to provide reactive power and improve the power factor of the generator. When a generator is connected to a load, the load may have a combination of resistive, inductive, and capacitive components. Inductive loads can cause the power factor of the generator to decrease, resulting in lower efficiency and voltage regulation. By adding a capacitor in parallel with the generator, the reactive power generated by the capacitor can offset the reactive power of the inductive load, leading to improved power factor correction. This helps to enhance the efficiency of power transfer and stabilizes the voltage. The capacitor absorbs and supplies reactive power, reducing the strain on the generator and ensuring a steady and efficient supply of electrical energy.