answersLogoWhite

0


Best Answer

code states that if a water source such as a sink is within 6 feet of a receptacle, that recetacle (s), must be protected by a GFCI receptacle.

I believe the actual distance is 5 feet. Please forgive me if I'm wrong. But the NEC also requires that ANY counter top receptacles in a kitchen and receptacles ANYWHERE in a bathroom must be GFCI protected.

More directly to your question, ordinary receptacles can be protected from a GFCI receptacle if properly wired. They are designed to do that. It is a way to save money. You may also consider a GFCI breaker if you have many receptacles to protect. I was told once that there is a limit of 3 "piggy backed" receptacles per GFCI but I have never seen that in the NEC.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can you feed multiple outlets to one GFCI outlet near the sink?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

Is a 15 amp 2 wire outlet wired with copper wire?

Yes it is wired with copper 2 wire is also known as 14/2 wire is use for switches,outlets,lights. and a 15a outlet should only be on a 15a breaker the main power feed to your meter to your panel is aluminum and can take more of a load than copper. In the US, 15 amp receptacles can be installed on 20 amp circuits if there is more than one receptacle on that circuit. Copper wire can carry a larger load than aluminum wire of the same size.


Will a bad plug receptable cause other switches to stop working?

It could! If wired in series in a way that is commonly done, linking receptacles on a common circuit, this especially true with GFCI outlets, allowing one GFCI to protect all outlets down stream. However, it would be unusual to find another type of device wired in this way. Regular receptacles have two screws on each side for the hot and neutral wires. A daisy chain of sorts is created when both blacks from two romex cables are connected to the two screws, and this continues down the wall to the next receptacle. Some problem with the receptacle or the wiring could cause a loss of power (or neutral) down the line. One that is obscure to the novice is the break -off tab near the screws. This is used when there is a switch controlling one of the out lets and the other is available as a standard outlet. If such an altered outlet is being reused, or one that some how was broken off, the two screws are no longer connected, and will not make the daisy chain as planned. It is common practice that circuit is provided to an area in new construction, and by code only seven or sometimes eight devices are allowed to be connected. Most often this a room light, some receptacles in that room and possibly receptacles in a wall common to another room. Depending on the routing of the "home run"...the wire from the breaker and the distribution panel... this could be any junction box that is part of this circuit. Problems here can affect any other part! Considering the possibilities of remodeling, upgrading to ceiling fan ...it is hard to tell. If necessary you may have to figure out witch box has the "home run" feed, disconnecting all there and reconstructing the circuits until the problem is isolated.


How to wire 4 prong generator plug?

Answer for USA, Canada and other countries running a 60 Hz supply service.Stop! What...? Don't try to do that...!Don't make a cable with the intention of plugging a generator into an outlet in your house, it is incredibly dangerous!Power from your generator will back-feed into the power lines, posing a severe unexpected shock hazard to any line-workers who may be fixing the lines - the very same reason you are wanting to use your generator!Plug your appliances directly into the outlets on your generator. If you want to power the outlets in your house from the generator you must do it right and install a proper 'generator transfer switch' at the main incoming breaker panel which is situated where the main electricity service cable comes into your house.As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.


Is there a device that will alarm if power goes out to a refrigerator outlet?

Don't know about a ready made device, but, it can be easily done. All you need is a relay, the coil of which is fed from the same power supply as the refrigerator outlet. Take a feed from a different circuit than that of the refrigerator outlet (eg a fed from a lighting circuit) and wire that through the Normally Open contact of the relay and then on to a simple sounder or alarm or electric bell etc, or even a warning light. An electrican could easily whip something like this up, i would think for minimal cost. Or if your keen u could do it yourself.Another answerJust Google "refrigerator alarm" and you should get some good results. Refrigerator alarms are available from as low as $9.99


Is a wire feed a mig or tig?

The wire feed welder is a MIG welder.

Related questions

Do all electrical outlets in a garage need to be GFCI?

Yes, but you can feed multiple outlets from one GFCI outlet. Make the first outlet fed in the cicuit a GFCI. Search for GFCI outlet with Google, etc. and I'm sure you will find an explanantion of how. Most GFCI's come with instructions also.


When running outlets in a series can you still use the outlet itself as a coupler or do you have to pigtail the wires then feed the outlet?

Just firmly connect the wires under the screws and that will couple them. Each outlet has two hot and two neutral screws; just connect the wires appropriately and make certain that the outlet is properly grounded.


Your lights and air quit working on your camper but the outlets still work has your inverter gone bad?

Not necessarily you should have a panel feed and a breaker may be tripped. If you have power in the outlet the converter is working.


Do I need two ground wires -one for each socket- if I split an outlet?

No. You can split the hot feeds and you can split the neutral feed, but both outlets of a standard duplex receptacle share the ground.


Why does the Outlet stops working after an appliance is plugged in?

Check for a loose wire connection on the sides of the outlet that you plug into that causes the other two outlets to stop working. Are the screws tight? There will probably be two wires on each side, one will be the feed coming to that oulet and the other one will feed to the other outlets. Also a possible loose connection in the box that the outlet is mounted in, such as a loose or broken wire in a wire nut. Remember to shut off the power to this circuit while working on it. I hope this will help. Polarity on the third outlet could be reversed. It will blow the circuit. Is it possibly current drain i.e are there too many outlets and is the appliance something that uses a lot of current? This can be discovered by reading the manual. If lets say the junction box or fuse box had been replaced by a solid wire then this would allow more current to flow. If this wire(fuse replaced) is supplying the three outlets and a short circuit is in the appliance. The first answer is correct. The other two may be true statements, but they do not address this question.


Will a gfci breaker work when neutrals and grounds are together in main panel or will there have to be a separate ground bar installed and wires separated?

Yes a GFCI will work if the neutrals and ground are to together the main panel. This is considered the line side of feed side of the GFCI. Neutral and ground can not touch down stream from the GFCI or on the load side of the GFCI.


Why will a light and one electrical outlet not work when the air gets warm?

Bad connections in the outlet or connector screws or it's feed connections at another oulet. Next time it quits bang on it and bang on the adjoining outlets. If one point causes a flicker - look for the problem there.


What is the difference between flex outlet and spur outlet?

A flex outlet is a wall outlet which has a flexible cable permanently wired into it instead of being fitted with a plug to go into a socket outlet. Flex outlets have their own fuse holder to replace the fuse which would normally be fitted into the plug if a fused plug were used instead. Such fused flex outlets are commonly used for electrical appliances which will never be moved, such as immersion heaters, which are permanently installed into domestic hot water storage tanks, and hot water heaters which are wall-mounted. A spur outlet is an additional wall outlet that is permanently connected to another wall outlet instead of being wired directly back to the breaker panel on its own circuit. Spur outlets are used occasionally when most socket outlets in a building are installed on a "ring main" and for some reason - usually because of cost when an additional socket outlet is found to be needed at a new point in the building - it was decided not to extend the ring main itself to that point in the building. A "ring main" is a loop of cable that goes out from a breaker to feed a "ring" of socket outlets in part of a building and then returns to be connected back to the same breaker. For instance in an average-sized house 3 ring mains would normally be installed: one for the socket outlets in the kitchen, one for the rest of the ground floor and the third for the bedroom floor. This method is used extensively in the UK and Eire where every appliance has its own correctly-fused plug.


Can I install several GFCI outlets on one circuit as it would be difficult to find the first plug on the line?

Generally, no, as GFCIs are designed for one to be a "master" and have the others feed off of it.


What would be the correct wiring for 3 sets of wires into a GFCI outlet?

I'm assuming your 3 sets of wires are black or red, or some other color normally associated with the "hot" wire, a white for neutral and a green or bare conductor for ground. If your GFCI protects only itself and no other receptacles, you splice all the wires of the same color together and attach 'pig tails' to your splice to connect to the GFCI. If your GFCI protects other receptacles 'down stream', you connect only the hot and neutral feed from the panel to the line side of the receptacle. Then you splice the others together as described above and connect your pig tails to the load side. "Line" and "load" should be clearly marked on the GFCI. Your ground in this case is still all spliced together with a pigtail for connection to the GFCI. Line is from the panel. Load is to other receptacles. Getting these reversed will prohibit your GFCI from functioning properly.


What's wrong with a 240V outlet that tests at 277V?

What's the reading at the service panel? What do regular 115V outlets read at? What kind of meter are you using? Chances are you have 480/277V 3 phase power to this building. Whoever wired the outlet used a 277V feed, possibly because 240V was not avaliable. You should call an electrician, repair of this problem may involve instalation of a transformer.


What is a store for animal feed called?

They are usually called feed stores, although similar products can be purchased at some grain mills and other outlets.