No. The breaker must protect the circuit components such as wiring, outlets and switches that are connected to the breaker. Therefore if you have a 30 amp circuit as dictated by its components you need to protect it with a 30 amp or less breaker.
Never upgrade the circuit breaker's amperage unless you have first upgraded the circuit. A 20-amp breaker will pop before a 12-AWG wire will melt. A 25-amp breaker cannot be relied upon to protect that same 12-AWG circuit.
Absolutely not. If you do this then there are several problems that will not trip the breaker, but will set fire to your house.
A dedicated 20 Amp circuit wired with 12/2 wiring an a 20 amp breaker.
A circuit breaker protects the wires that the devices are connected to. If the devices that are connected to the circuit are 20 amps the wire size should be #12 wire fed from a 20 amp breaker. This breaker should not trip unless the circuit is overloaded or a fault occurs on the circuit. If the devices that are connected to the circuit are15 amps the wire size should be #14 wire fed from a15 amp breaker. This breaker should not trip unless the circuit is overloaded or a fault occurs on the circuit. Putting 20 amp sockets on this 15 amp circuit will work but the circuit is limited to the amount of load that can be plugged in. You will not get the full capacity of the 20 socket because the breaker will trip at 15 amps.
No, you should not install a 30 amp circuit breaker to a machine which normally requires a 20 amp supply. The circuit breaker is protecting the wire to the machine. That wire is likely only rated for 20 amps, (# 12 awg). Therefore, a 30 amp breaker could allow too much current to go through the wiring to the machine and cause the wire to burn down. Replace the 3 phase 20 amp breaker with the same amperage breaker.
No tandem breakers are of the same value.
For a continuous load the circuit breaker is set 25% higher than the load current. So a 20-amp breaker is used with a continuous 16-amp load.
A dedicated 20 Amp circuit wired with 12/2 wiring an a 20 amp breaker.
A 32 amp fixture can not be fed from a 20 amp breaker as the breaker will trip every time.
A circuit breaker protects the wires that the devices are connected to. If the devices that are connected to the circuit are 20 amps the wire size should be #12 wire fed from a 20 amp breaker. This breaker should not trip unless the circuit is overloaded or a fault occurs on the circuit. If the devices that are connected to the circuit are15 amps the wire size should be #14 wire fed from a15 amp breaker. This breaker should not trip unless the circuit is overloaded or a fault occurs on the circuit. Putting 20 amp sockets on this 15 amp circuit will work but the circuit is limited to the amount of load that can be plugged in. You will not get the full capacity of the 20 socket because the breaker will trip at 15 amps.
If i understand you correctly, yes there certainly can be. If you replace, say a 10 amp breaker with a 20 amp. you are losing the safety factor - the whole purpose of the breaker to begin with. Always replace a breaker with the exact same amperage rating!
No, you should not install a 30 amp circuit breaker to a machine which normally requires a 20 amp supply. The circuit breaker is protecting the wire to the machine. That wire is likely only rated for 20 amps, (# 12 awg). Therefore, a 30 amp breaker could allow too much current to go through the wiring to the machine and cause the wire to burn down. Replace the 3 phase 20 amp breaker with the same amperage breaker.
No tandem breakers are of the same value.
For a continuous load the circuit breaker is set 25% higher than the load current. So a 20-amp breaker is used with a continuous 16-amp load.
No more than 13 maximum on a 20 amp circuit.
Yes, provided that you don't really need 20 A on the circuit.
Usually a 15 or 20 amp breaker is sufficient
You use the correct size breaker depending on the size wire in the circuit. If the circuit is wired with AWG #12 wire use a 20 amp breaker. If it is wired with AWG #14 wire then use a 15 amp breaker.
If the fault was on the 20 amp branch circuit, the branch circuit breaker should have tripped, not the main breaker. Call a qualified electrician to check out your wiring.