Want this question answered?
To answer this question a voltage needs to be stated. Wire is sized by the amount of amperage the load takes. W = Amps x Volts. Amps = 650/ volts.
The V stands for volts and A is amps. If for example you have a 12kVA device and are running off a voltage of 120 volts then Amps = 12000/120 = 100. You then use the calculated amps in a wire size table to get the correct size.
Yes, if you are using AWG # 10 wire. If you are using AWG # 12 then the answer is no you must use a 20 amp breaker. On AWG #14 wire you must use a 15 amp breaker.
6 AWG will handle 50 amps with a voltage drop of about 4 volts. If you go to 4 AWG and limit to 50 amps your voltage drop will be 2.5 volts.
AWG # 10.
15 amps
30 amps.
To answer this question a voltage needs to be stated. Wire is sized by the amount of amperage the load takes. W = Amps x Volts. Amps = 650/ volts.
Wire gauge is determined by the capacity in amps. At 120 volts it requires 8.33 amps to provide 1000 watts. The typical residential application would require 18 AWG wire 1.024 mm in diameter.
Amps * Volts = Watts So, Watts / Volts = Amps 2000 / 240 = 8.333 Amps You should run the circuit on a two pole 15 Amp breaker, using 14 AWG, 2 conductor (plus ground) wire, just so you have a little safety factor in the circuit size.
A # 14 copper conductor will be fine to carry 8 amps at 120 volts. This size conductor is rated at 15 amps.
At 120 Volts you would draw about 42 amps. At 240 Volts it would be about 21 amps. For 120 Volts you would need 6 AWG and for 240 Volts you would need 10 AWG.
The first thing we have to do is clarify between the two items. 120 volt wire rating is an insulation rating of the wire. Like wire with ratings of 300 volts, 600 volts and 1000 volts these are the highest allowable voltages that can be applied. A wire that is rated for 300 volts is good for 120 volts, 240 volts and 277 volts. At test research facilities, equipment is tested to destruction. The label that is given to wire as a result of the tests is the highest safest voltages that can be applied to that particular wire. So when you see a wire that has a label stating that it is rated for 300 volts it means that any voltage under and up to 300 volts is safe to apply. The ability of a wire to carry current (amps) is related to the size of the wire. Now, watts is the product of amps x volts. To answer this question, assuming the supply voltage is 110 volts, an amperage needs to be stated as per the formula above.
The V stands for volts and A is amps. If for example you have a 12kVA device and are running off a voltage of 120 volts then Amps = 12000/120 = 100. You then use the calculated amps in a wire size table to get the correct size.
5 amps
3/0 wire 3/0 wire
A #14 wire will do the job.