This is one of those cases where if you don't know, you shouldn't do it.
The house doesn't have the drywall up yet, correct?
I would call an electrician. The guy will come out and tell you what to buy. You buy it and bring it home. He brings his helper and installs it. I've seen some electricians who'll show you how to pull the wire yourself--this is the part that is easy. You pull the wire, and he hooks it up for you. Other electricians want to do it all themselves.
You probably blew the breaker for the lights. While usually the lights and outlets in a room are on the same breaker, it isn't always done that way. And you may have blown the light bulbs in the lights.
A GFCI receptacle can pass it's "protection" to other outlets wired from it. If the GFCI trips, all outlets wired from it will "trip" also. A GFCI tripping will not necessarily trip the circuit breaker in the service panel.
A 15 amp breaker protecting # 14 wire.
If there is any additional load on the outlets greater than 2.5 amps the breaker will trip. Loads of 1500 watts should be on a dedicated breaker. If the total load exceeds 15 amps the breaker will operate. However many of the outlets might supply only lights, TVs or nothing at all, so in those conditions it's OK.
You can provided the protecting breaker for the circuit is 20 Amps or less.
You probably blew the breaker for the lights. While usually the lights and outlets in a room are on the same breaker, it isn't always done that way. And you may have blown the light bulbs in the lights.
A GFCI receptacle can pass it's "protection" to other outlets wired from it. If the GFCI trips, all outlets wired from it will "trip" also. A GFCI tripping will not necessarily trip the circuit breaker in the service panel.
A 15 amp breaker protecting # 14 wire.
If there is any additional load on the outlets greater than 2.5 amps the breaker will trip. Loads of 1500 watts should be on a dedicated breaker. If the total load exceeds 15 amps the breaker will operate. However many of the outlets might supply only lights, TVs or nothing at all, so in those conditions it's OK.
You can provided the protecting breaker for the circuit is 20 Amps or less.
It means the breaker has been tripped. There are two possible ways to reset it - some have a button on the outlet (there may be several outlets on one circuit, so you may have to look around) the other is the main breaker in your breaker box. You'll need to find a reset the breaker.
In a well designed house the lights are not connected to the same circuit as an appliance. If by going out you are saying that a breaker trips, then your appliances and lights combined are exceeding the rating of the breaker. You either need to rewire and balance the loads better or plug high current appliances into different outlets on another breaker. If you are not tripping breakers, but lights are just dimming you have a bigger problem with inadequate current supplying your house.
No, the whirlpool has a motor load connected to it and should be connected to a dedicated ground fault breaker.
The only determining factor is the size of the circuit breaker that you will be using. If the garage circuit will be protected with a 15 Amp breaker, you may use a 14 AWG wire. If the circuit will be protected with a 20 amp breaker, you must use a 12 AWG wire. Note too that garage outlets should be protected with a GFCI breaker or outlet. If you have any concerns regarding your ability to adequately design and install the garage outlets, please, for your own safety, contact a local electrician.
A 30 amp breaker is usually used for a dedicated 30 amp device. Ordinary 15 amp receptacles can not be connected to a breaker of higher trip capacity than the rating of the receptacle. The wire size for a 30 amp breaker is #10 AWG.
Not necessarily you should have a panel feed and a breaker may be tripped. If you have power in the outlet the converter is working.
120 amps The above answer is wrong. A 60 amp breaker is designed to trip at 60 amps be it a single pole, double pole or a triple pole that is used on three phase equipment. The number on the handle of a breaker is the trip capacity.