At 240 volts, and 7 amp current, you will have a load of 1680 watts (volts x amps = watts). A 2000 watt generator will sufice, however a 3500 watt generator, if within your budget, will power a few other necessities if required.
Check and see what the amperage the A/C unit draws. These types of appliances should have their own dedicated circuit. If there is nothing of a high load on the existing 120 volt circuit and the A/C unit draws less than 12 amps, the unit should operate without tripping the breaker. If the A/C unit only has wattage and no amperage shown on the nameplate use this equation to find the amperage. I = W/E, Amps = Watts/Volts.
The current will remain in a 220 volt circuit as long as the circuit load remains in the circuit and the circuit remains closed.
Yes, but it may draw too much current for the circuit. If it's a 15 amp circuit and the welder draws 17 amps, it won't work. Voltage is only a part of the puzzle.
Yes, in the form of GFCI circuit breakers, not as a receptacle.
No, not a good idea. You have to use a 347 volt ballast.
Yes, but the motor's horsepower rating will not be reached.
When the term "double 20 amp circuit" is used, the presumption is that, it is 20 amps at 240 volts. If your generator has the breaker built in then, yes, you have the capacity to run 240 volt devices from your generator.
Because its designed to operate at 230-460, not 120-208.
240 ohms
Check and see what the amperage the A/C unit draws. These types of appliances should have their own dedicated circuit. If there is nothing of a high load on the existing 120 volt circuit and the A/C unit draws less than 12 amps, the unit should operate without tripping the breaker. If the A/C unit only has wattage and no amperage shown on the nameplate use this equation to find the amperage. I = W/E, Amps = Watts/Volts.
A volt can not be connected to a circuit.
You need a step-up transformer, to go from 110 to 220-240 volts. Then a 110 volt supply can operate 240 volt equipment.
It depends on how much power the lamps require, and on how they are connected.
No, the generator must output 220 volts which any generator I have ever seen does.
No.
The current will remain in a 220 volt circuit as long as the circuit load remains in the circuit and the circuit remains closed.
Yes, Power (in watts) equals voltage times current (Amps). Amps = Watts/Volts If your generator is 6000 watts that would operate a 120 volt load up to 50 amps (6000/120=50). If you are running a motor or compressor, the initial inrush of current is about 3 times higher so 14 X 3 = 42amps. Should do fine...