Q: How many amps can you run through 200 feet of number 8 aluminum wire?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

What size aluminum wire needed for 30 amp at 240 volt for 500 feet underground?

A 1/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 30 amps for 500 feet on a 240 volt system.


What size aluminum wire for 100 amps undergroundservice 60 feet from meter?

A 3/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 150 amps for 150 feet on a 240 volt system. This size will allow the conductor to be loaded to 120 amps. 150 x 80% = 120 Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 150 amps then you would need to use a wire with a rating of 190 amps. 190 x 80% = 152 amps A 4/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 190 amps for 150 feet on a 240 volt system.


What gauge wire for aluminum 240 volts 20 amp 200ft?

A #6 aluminum conductor will limit the voltage drop to 3% or less when supplying 20 amps for 200 feet on a 240 volt system.


What size aluminum wire to feed 125 Amps 220 volt a distance of 175' and what size ground?

A 3/0 aluminum conductor will limit the voltage drop to3% or less when supplying 125 amps for 175 feet on a 220 volt system. If the 125 amp load is a sub distribution panel that is not going to be fully loaded to 125 amps then using the exact connected load, which might be smaller than 125 amps will effect the wire sizing. The grounding conductor for that size distribution panel is #6 bare copper.


What size aluminum wire needed for 60 amp at 240 volt for 330 feet underground?

A 1/0 AWG aluminium conductor will limit the voltage drop to 3% or less when supplying 60 amps for 330 feet on a 240 volt system. The cable will be rated as ACWU 90. ACWU 90 cables are primarily intended for exposed and concealed wiring in dry or wet locations and where exposed to the weather. For use in ventilated, non-ventilated, and ladder type cable trays in wet and dry locations; direct earth burial; service entrance above or below ground.

Related questions

What size aluminum wire needed for 30 amp at 240 volt for 500 feet underground?

A 1/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 30 amps for 500 feet on a 240 volt system.


What size aluminum wire for 100 amps undergroundservice 60 feet from meter?

A 3/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 150 amps for 150 feet on a 240 volt system. This size will allow the conductor to be loaded to 120 amps. 150 x 80% = 120 Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 150 amps then you would need to use a wire with a rating of 190 amps. 190 x 80% = 152 amps A 4/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 190 amps for 150 feet on a 240 volt system.


What gauge wire for aluminum 240 volts 20 amp 200ft?

A #6 aluminum conductor will limit the voltage drop to 3% or less when supplying 20 amps for 200 feet on a 240 volt system.


What size aluminum wire to feed 125 Amps 220 volt a distance of 175' and what size ground?

A 3/0 aluminum conductor will limit the voltage drop to3% or less when supplying 125 amps for 175 feet on a 220 volt system. If the 125 amp load is a sub distribution panel that is not going to be fully loaded to 125 amps then using the exact connected load, which might be smaller than 125 amps will effect the wire sizing. The grounding conductor for that size distribution panel is #6 bare copper.


What size aluminum wire needed for 60 amp at 240 volt for 330 feet underground?

A 1/0 AWG aluminium conductor will limit the voltage drop to 3% or less when supplying 60 amps for 330 feet on a 240 volt system. The cable will be rated as ACWU 90. ACWU 90 cables are primarily intended for exposed and concealed wiring in dry or wet locations and where exposed to the weather. For use in ventilated, non-ventilated, and ladder type cable trays in wet and dry locations; direct earth burial; service entrance above or below ground.


How many amps will 2-2-2-4 carry at 180 feet?

150 amps


How many amps can 16 gauge wire carry at 120 vac at 25 feet?

18 amps.


How do you make 3.2808399 through a feet stick?

Without a given unit, you can not make that number through a feet stick. You need to include a unit in order to indicate the number on the stick.


What gauge wire to deliver 15 amps at 1000 feet?

12


How many amps will 10-2 wire carry at 40 feett?

30 amps is how much a 10-2 wire will carry at 110 feet. 10 gauge wire is only good for thirty amps per the national electrical code. Using 80% of the breakers usage you will actually be getting only 24 amps.


Do your feet get bigger when you go through menopause?

no, you may have swollen feet for a number of other reasons, this is a question for your gynacologist after he has diagnosed you.


Need to run 30 amps about 100 feet what copper wire?

This is a voltage drop question. A voltage at 30 amps needs to be stated to answer the question.