One View:In USA: As many as you want. There's no magic number. You have 15A to play with, so you can divide that up however you wish. It all depends on what you intend to plug in. For general usage I'd stick with the NEC Code (any point along a wall must be within 6ft of a receptacle).

In my 1970's house here I've counted 9 receptacles on a single 15A breaker (yuck!).

Always be sure to switch off the breakers at the main panel before you attempt to do any work on any mains power circuit.

Another View:Yes there are some "magic numbers".The U.S. National Electrical Code Article 220.3 (B) (9) has guidelines for calculatiing general 120 volt dwelling-unit receptacle circuits as having a load of 180 volt-amps per receptacle.

Because a normal circuit breaker can only be loaded to 80 percent of trip rating, then 0.80 X 15 = 12 Amps. 12 Amps X 120 volts = 1440 Volt-Amps per 15-Amp circuit. 1440 VA / 180 VA per receptacle = 8 duplex receptacles per circuit allowed.

For a 20-Amp circuit, you are allowed (.8 x 20 X 120)/ 180 = up to 10 duplex receptacles per circuit.

Another View:Both answers are technically correct.

A device (receptacle, switch etc) by definition does not consume any energy so there is no load added to the circuit by installing any number of receptacles. The problem occurs when too many loads are plugged into those receptacles.

The NEC section quoted above (moved to 220.14 (I) in 2008) does not apply to receptacles used for general illumination in a dwelling (which covers a majority of household receptacles). Dwellings are addressed by NEC 220.14 (J).

Further, the 80% quoted is true for continuous loads only. If the appliances being switched on and off on a particular circuit never run continuously all at the same time, their individual wattages when totalled-up can, in fact exceed that 80% figure, because a non-continuously-loaded breaker may have 100% of its rating applied to it for short periods such that it does not become "warm"...

<><><>

A good guideline many electricians follow as a 'rule of thumb' is of 1.5 amps per receptacle.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar
More answers
User Avatar

AnswerBot

5mo ago

In general, you can wire multiple receptacles to a 15 amp circuit, but the exact number will depend on the total load of the devices being plugged in and the wiring configuration. It is recommended to follow local electrical codes and guidelines to ensure safety and avoid overloading the circuit.

This answer is:
User Avatar

User Avatar

Wiki User

15y ago

eight In Canada there shall be not more that 12 outlets on any 2 wire branch circuit. Such outlets shall be considered to be rated at not more that 1 amp per outlet. Where the connected load is known, the number of outlets may exceed 12 providing the load current does not exceed 80 % of the rating of the over current device protecting the circuit.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago
Answer for USA, Canada and countries running a 60 Hertz supply service.
Circuit loading
The code states that there shall be not more that 12 outlets on any 2 wire branch circuit. Such outlets shall be considered to be rated at not more that 1 amp per outlet. Where the connected load is known, the number of outlets may exceed 12 providing the load current does not exceed 80 % of the rating of the over current device protecting the circuit.

<<>>

That depends on what the circuit will be used for.
I'd put a refrigerator on a 15 amp circuit and not anything else.
For a typical bedroom or living room circuit, about 5 outlets.
For 100 watt ceiling lights, again, about 5.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago
Answer for USA, Canada and countries running a 60 Hertz supply service.

Builders generally hook up to 8 outlets and/or lights per circuit.

Builders should not be doing electrical installations.

In Canada there shall be not more that 12 outlets on any 2 wire branch circuit. Such outlets shall be considered to be rated at not more that 1 amp per outlet. Where the connected load is known, the number of outlets may exceed 12 providing the load current does not exceed 80 % of the rating of the over current device protecting the circuit.

A 15 amp breaker can supply 1800 watts total for lights, outlets, etc. (15 X 120 volts= 1800 watts). As a rule of thumb leave 20% "spare" in the event you connect a power hungry item - 1440 watts total. Add up the total wattage of items you plan to plug in to the circuit.

This only applies to commercial properties.

There is no strict limit on how many receptacles can be connected to a 15 amp breaker in a residential property according to the NEC. The device is a convenience outlet and they are placed for convenient access to power without creating hazards [crossing doorways, etc]

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

Depends on the anticipated loads. Six would be a typical layout in a residence.

There is no restriction on the number of outlets on a circuit in a residential setting, however the circuit should only serve 500 square feet of the dwelling.

This answer is:
User Avatar

User Avatar

Wiki User

10y ago

Depends on the size wire used in the circuit. If you wired the circuit with AWG #12 wire on a 20 amp breaker then you can install no more than 12 outlets. If you wired it with AWG #14 wire on a 15 amp breaker then install no more than 9 outlets. This is assuming only outlets are on the circuit and nothing else.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

15A x 120V = 1800 VA

NEC allows 180 VA per receptacle

1800/180 = 10 receptacles

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How many receptacles can you wire to a 15 amp?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

How many 15 amp receptacles can you put on a 15 amp breaker?

You can typically install multiple 15 amp receptacles on a 15 amp breaker, but the exact number will depend on the specific electrical code regulations in your area and the overall electrical load on the circuit. It's important to ensure that the total load does not exceed the capacity of the breaker to prevent overloading and potential safety hazards.


Can a 20 amp circuit breaker operate two 15 amp receptacle?

It is perfectly acceptable to have (2) 120 volt 15 amp receptacles operated from a 120 volt 20 amp circuit breaker (as a general rule of thumb 11 receptacles are acceptable on a 20 amp circuit). The 15 amp rating of the receptacle is the maximum allowed amperage that should be hooked up to the receptacle at any one time. So in this case the limiting factor is the amount of current being drawn across both receptacles simultaneously should not exceed the 20 amp rating of the circuit breaker. In the United States the NEC code allows the use of a 20 amp circuit breaker to feed a branch circuit consisting of 15 amp receptacles. Generally you would not exceed 11 receptacles though as you will assume an average load of 1.5 amps per receptacle and trying to maintain about 80% max load.


What is a common branch circuit connector?

There are many variables that affect the ratings of electrical circuits but in general: If you are asking about residential branch circuit ratings, they are listed in amps and protected by a fuse or breaker. For example, a typical residential lighting circuit is usually a 15 amp / 120 volt circuit. It will be protected by a 15 amp overcurrent device (breaker or fuse) and all components of the circuit (wire etc) must be rated for at least 15 amps. Common residential circuit ratings: 15 amp / 120 volt - lighting and receptacles 20 amp / 120 volt - bathroom, kitchen, dining room, workshop etc. receptacles 30 amp / 240 volt - electric dryer, electric water heater 40 or 50 amp / 240 volt - electric stove For minimum conductor (wire) sizing, the National Electric Code recognizes many variables that affect the ampacity (number of amps) a wire can safely carry. But in most residential circuits the following copper conductors are used: 15 amp - #14 American Wire Gauge (AWG) 20 amp - #12 AWG 30 amp - #10 AWG 40 amp - #8 AWG 50 amp - #6 AWG Aluminum is typically not used in the smaller sizes, though you may find #6 AWG used for larger (40 amp) loads


How many plugs with 15 amp 14 gauge wire?

Using 14 gauge wire with a 15 amp circuit breaker, you typically can have around 8-10 receptacles per circuit, depending on local electrical code regulations. It's important to consult with a licensed electrician to ensure the proper number of outlets for your specific setup.


Can you control 10 outlets with one 20 amp GFCI outlet on one 20 amp circuit?

If each outlet draws less than 2 amps, then you could control 10 outlets with a 20 amp GFCI outlet on a 20 amp circuit. However, it's worth consulting an electrician to ensure the load calculations are accurate and the wiring is safe for the intended use.

Related questions

How many electrical receptacles on 15 A breaker with 12 gauge wire?

In the United States and according to the NEC, in commercial and industrial installations, you are limited to 10 receptacles on a 15 amp circuit. The size of the wire is not a determining factor. There is no limit to the number of receptacles on a circuit in a home and there may be local codes where you live that have stricter requirements.


What receptacles will except a 15 amp attachment plug?

Many receptacles will. First you need to tell us if you are in north America, UK or Australia.


How many 15 amp receptacles can you put on a 15 amp breaker?

You can typically install multiple 15 amp receptacles on a 15 amp breaker, but the exact number will depend on the specific electrical code regulations in your area and the overall electrical load on the circuit. It's important to ensure that the total load does not exceed the capacity of the breaker to prevent overloading and potential safety hazards.


Can you use 40 amp breaker for your lights and plug ins?

If you are referring to house wiring then the answer is no. A breaker protects the wire size that is connected to the breaker. In home wiring most homes are wired with a #14 wire which is rated at 15 amps. That is why the wire is protected by a 15 amp breaker. The correct wire size to connect to a 40 amp breaker is a #8. This size wire is too large to connect to receptacles an light fixture terminals.


What are electrical receptacles?

The terminology in North America it is used for wall outlets. The majority of receptacles used in homes are duplex receptacles. The device consists of one upper and one lower connection point that are rated at 15 amp capacity. The receptacle can be converted to two individual 15 amp circuits by removing a tie bar between the upper and lower connection points. This type of installation has to be connected by a three wire cable.


Receptacles for 15 AMP circuit?

Common throughout a house. Widely available.


What is a 15 amp electrical outlet?

A #14 copper wire rated at 15 amps is the minimum size wire for a 15 amp receptacle.


Can a 20 amp circuit breaker operate two 15 amp receptacle?

It is perfectly acceptable to have (2) 120 volt 15 amp receptacles operated from a 120 volt 20 amp circuit breaker (as a general rule of thumb 11 receptacles are acceptable on a 20 amp circuit). The 15 amp rating of the receptacle is the maximum allowed amperage that should be hooked up to the receptacle at any one time. So in this case the limiting factor is the amount of current being drawn across both receptacles simultaneously should not exceed the 20 amp rating of the circuit breaker. In the United States the NEC code allows the use of a 20 amp circuit breaker to feed a branch circuit consisting of 15 amp receptacles. Generally you would not exceed 11 receptacles though as you will assume an average load of 1.5 amps per receptacle and trying to maintain about 80% max load.


Is 26 receptacles wired on one 15 amp breaker up to code or standard practice for residential 26 receptacles include 10 can lights 4 other lights 12 outlets?

NO! You are drastically in excess of electrical code requirement. A 15 amp circuit should not exceed eight total receptacles and/or lighting devices.


What is a common branch circuit connector?

There are many variables that affect the ratings of electrical circuits but in general: If you are asking about residential branch circuit ratings, they are listed in amps and protected by a fuse or breaker. For example, a typical residential lighting circuit is usually a 15 amp / 120 volt circuit. It will be protected by a 15 amp overcurrent device (breaker or fuse) and all components of the circuit (wire etc) must be rated for at least 15 amps. Common residential circuit ratings: 15 amp / 120 volt - lighting and receptacles 20 amp / 120 volt - bathroom, kitchen, dining room, workshop etc. receptacles 30 amp / 240 volt - electric dryer, electric water heater 40 or 50 amp / 240 volt - electric stove For minimum conductor (wire) sizing, the National Electric Code recognizes many variables that affect the ampacity (number of amps) a wire can safely carry. But in most residential circuits the following copper conductors are used: 15 amp - #14 American Wire Gauge (AWG) 20 amp - #12 AWG 30 amp - #10 AWG 40 amp - #8 AWG 50 amp - #6 AWG Aluminum is typically not used in the smaller sizes, though you may find #6 AWG used for larger (40 amp) loads


Is a 15 amp 2 wire outlet wired with copper wire?

Yes it is wired with copper 2 wire is also known as 14/2 wire is use for switches,outlets,lights. and a 15a outlet should only be on a 15a breaker the main power feed to your meter to your panel is aluminum and can take more of a load than copper. In the US, 15 amp receptacles can be installed on 20 amp circuits if there is more than one receptacle on that circuit. Copper wire can carry a larger load than aluminum wire of the same size.


How do you wire a 15 amp circuit?

Use a 15 amp breaker and 14 AWG wire and all switches and outlets rated at 15 amps or greater.