answersLogoWhite

0


Best Answer

A 15 amp breaker will trip at 15 amps at an ambient temperature of 104 degree F. If the ambient temperature is higher the breaker will trip before 15 amps and if the ambient temperature is lower the breaker will trip after 15 amps. I would suspect the circuit is overloaded. But, you can change the breaker and see what happens. Just swap it with another one.

User Avatar

Wiki User

10y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: I have a 15 amp tool hooked up to a 15 amp breaker- This trips the breaker even with nothing else running- There is also a GFCI outlet on the same circuit- Is the breaker or GFCI bad?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

Can I you use existing 8 3 wire hooked to a 30amp breaker was hooked to old electric heater to wire a heater that requires 10 2 wire its a 5000watt 240volt heater?

Yes the wire size is larger for that size breaker but will not effect the 30 amp breaker protection of that circuit.


Why fuse wire is placed in series with the device?

circuit breaker and fuses used in series to break the circuit in overcurrent situation to block current to flow through circuit.


Can 105 amp be hooked too one breaker pole?

Go to the discussion tab and explain what you are trying to do.


Can a 20 amp circuit breaker operate two 15 amp receptacle?

It is perfectly acceptable to have (2) 120 volt 15 amp receptacles operated from a 120 volt 20 amp circuit breaker (as a general rule of thumb 11 receptacles are acceptable on a 20 amp circuit). The 15 amp rating of the receptacle is the maximum allowed amperage that should be hooked up to the receptacle at any one time. So in this case the limiting factor is the amount of current being drawn across both receptacles simultaneously should not exceed the 20 amp rating of the circuit breaker. In the United States the NEC code allows the use of a 20 amp circuit breaker to feed a branch circuit consisting of 15 amp receptacles. Generally you would not exceed 11 receptacles though as you will assume an average load of 1.5 amps per receptacle and trying to maintain about 80% max load.


In The USA How many outlets can be hooked up on a 20 amp circuit?

Rule of thumb is about 8 unless it is a dedicated circuit. The NEC has no requirements on the number of receptacles that can be on a circuit in a residential setting. The circuit should be layed out to only cover 500 sq. feet. A single room of 500 sq. feet, you could put as many receptacle as you want on one circuit.

Related questions

Can I you use existing 8 3 wire hooked to a 30amp breaker was hooked to old electric heater to wire a heater that requires 10 2 wire its a 5000watt 240volt heater?

Yes the wire size is larger for that size breaker but will not effect the 30 amp breaker protection of that circuit.


What is a difference between 10KA and 22KA circuit breakers?

The previous answer is incorrect, and I would advise that user to not give out information if they are going to give completely misguided information. The interrupting rating of a breaker is the maximum current that the breaker is designed to handle, at the breaker's rated voltage, before damage will occur to the breaker. A breaker will trip at FAR LESS than the interrupting rating, but it is extremely dangerous to expose the breaker to any situation where it will have more than the rated interruption current. the breaker is designed for. The reason some breakers are rated at 22kA instead of 10kA is because they typically have far larger conductors hooked up to them, so with the lowered impedance on the circuit there is more of a chance for the breaker to experience a higher fault current at the breaker. So electricians install 22kA breakers to handle the higher "available fault current."


What causes an electrical surging sounds be when home ac unit is running?

The wiring to the unit is either not on the right type of breaker switch or the unit is not hooked up directly to the breaker box at all.


Why fuse wire is placed in series with the device?

circuit breaker and fuses used in series to break the circuit in overcurrent situation to block current to flow through circuit.


When converting from 240V 50A electric range to gas range with a 120V 15A dedicated circuit can you use the now useless 240v circuit for the lower voltage range or should you start from scratch?

Just use one of the hot wires and cap the other. Since you are changing the breaker, the unused line will not be hooked to anything. There is really nothing to be gained by pulling new wire.


Will an alternator put out power if not hooked up to a battery and y?

No, the battery is part of it's circuit. In fact nothing in the car will work without the battery.


What kind of circuit is formed when resistors are hooked up to side to side?

parallel circuit


What kind of circuit is formed when resistors are hooked up side to side?

parallel circuit


What circuit breaker acts as a switch creating an circuit when current is too high?

No. circuit breakers are in series with whatever lines they are protecting. They are never put in parallel with the protected loads (this would defeat the purpose). Circuit breakers open resulting in an open circuit / no power to outlets when they trip.


What instrument is hooked to galvanometers?

Your question is confused. A galvanometer is an instrument, it is not hooked to an instrument. It is hooked to an electrical circuit of some kind, to measure how much electricity is flowing.


Can 105 amp be hooked too one breaker pole?

Go to the discussion tab and explain what you are trying to do.


Can a 20 amp circuit breaker operate two 15 amp receptacle?

It is perfectly acceptable to have (2) 120 volt 15 amp receptacles operated from a 120 volt 20 amp circuit breaker (as a general rule of thumb 11 receptacles are acceptable on a 20 amp circuit). The 15 amp rating of the receptacle is the maximum allowed amperage that should be hooked up to the receptacle at any one time. So in this case the limiting factor is the amount of current being drawn across both receptacles simultaneously should not exceed the 20 amp rating of the circuit breaker. In the United States the NEC code allows the use of a 20 amp circuit breaker to feed a branch circuit consisting of 15 amp receptacles. Generally you would not exceed 11 receptacles though as you will assume an average load of 1.5 amps per receptacle and trying to maintain about 80% max load.