Best Answer

No, the conductor is too small. The feeder to a 120/240 volt sub panel should be a 1/0 copper or a 2/0 aluminium conductor. This size conductor will limit the voltage drop to 3% or less when supplying 125 amps for 125 feet on a 240 volt system. ACWU 90 (Armoured Cable Wet location Underground 90 degree C). ACWU 90 cable is code approved for direct burial and is used in many projects as an underground service distribution feeder. Aluminium is much cheaper than copper for this type of installation.

User Avatar

Wiki User

8y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Should a 2 AWG copper wire be used to feed a 125 amp sub panel located 125 feet from main panel?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What size wire is needed to feed a 125 amp sub panel from a 200 amp panel less than 200 wire feet away?

A #1 copper wire with an insulation rating of 90 degrees C is rated at 140 amps.


Can you feed a 60 amp sub panel from another 60 amp sub panel?

Yes


Can you run an additional breaker panel parallel to the existing one?

It is not in parallel. You put a breaker in existing panel and use that to feed the subpanel. The Amperage of this subfeed breaker should match the rating of the new panel. For example a 100A breaker might be typical. Remember that ground and neutral are only "bonded" at the main panel. Usually a subpanel has a means to separate the neutral and ground in a subpanel. Be careful since everything about doing this is dangerous.Another AnswerYes, you can have two breaker panels in parallel. If you had a 100 amp panel on a 200 amp service (or increase the size of the service, check with your power company on the size of your service, you could add a second 100 amp panel in parallel with the first. You can have up to 6 disconnects per service, but they must be located adjacent to each other or in the same enclosure. So either install the second panel beside the first or a 100 amp disconnect beside the first panel and feed out of the disconnect to the new panel located where you need it.


Can you tie the neutral wire on a sub feed to another panel to the main neutral lug?

no


What is the wire size needed to feed a 400 amp service with parallel copper?

It depends on the length of the run

Related questions

Why does your solar hot water system not get hot?

The solar panel pumps are not working,then may be solar panel copper tubes block,may be water not store in feed water tank.


What size wire is needed to feed a 125 amp sub panel from a 200 amp panel less than 200 wire feet away?

A #1 copper wire with an insulation rating of 90 degrees C is rated at 140 amps.


I have a Transformer 480 primary 208 secondary feeding 1 200amp mb 42 space panel I need to feed a subpanel 6 ft away I'm thinkin feed through lug at top of bus or at feed through MB suggestions?

The sub-panel need to be fed from the main panel, by way of a circuit breaker connected to one of the breaker locations. Or if your sub-panel has a main breaker installed you can feed from the main panel with a sub-feed lug kit. This looks like a breaker, but is only a point where you can branch off the sub panel.


Can you feed a 60 amp sub panel from another 60 amp sub panel?

Yes


Can you run an additional breaker panel parallel to the existing one?

It is not in parallel. You put a breaker in existing panel and use that to feed the subpanel. The Amperage of this subfeed breaker should match the rating of the new panel. For example a 100A breaker might be typical. Remember that ground and neutral are only "bonded" at the main panel. Usually a subpanel has a means to separate the neutral and ground in a subpanel. Be careful since everything about doing this is dangerous.Another AnswerYes, you can have two breaker panels in parallel. If you had a 100 amp panel on a 200 amp service (or increase the size of the service, check with your power company on the size of your service, you could add a second 100 amp panel in parallel with the first. You can have up to 6 disconnects per service, but they must be located adjacent to each other or in the same enclosure. So either install the second panel beside the first or a 100 amp disconnect beside the first panel and feed out of the disconnect to the new panel located where you need it.


Is a 15 amp 2 wire outlet wired with copper wire?

Yes it is wired with copper 2 wire is also known as 14/2 wire is use for switches,outlets,lights. and a 15a outlet should only be on a 15a breaker the main power feed to your meter to your panel is aluminum and can take more of a load than copper. In the US, 15 amp receptacles can be installed on 20 amp circuits if there is more than one receptacle on that circuit. Copper wire can carry a larger load than aluminum wire of the same size.


Can goats eat a feed with a high tolerance of copper?

Yes. Unlike sheep, goats actually need copper in their diet. Goat feed usually includes copper, as do goat-specific mineral blocks.


how much should i feed my bog?

How much should I feed my dog or, how much should you feed your dog


Where should a service valve be located in order to isolate the supply from the hot water storage vessel to the tap?

Cold feed


What is IP Electronic Battery Feed Fuse?

It' the fuse for your Instrument Panel Battery


how much should you feed your pet?

in everyday i should feed my pet


How should you feed a Snowy Owl?

You should feed it slowly and steadily.