answersLogoWhite

0


Best Answer

A #1 copper conductor will limit the voltage drop to 3% or less when supplying 95 amps for 200 feet on a 208 volt system. This size will allow the conductor to be loaded to 76 amps. 95 x 80% = 76 amps

Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 95 amps then you would need to use a wire with a rating of 120 amps. 120 x 80% = 96 amps.

A 1/0 copper conductor will limit the voltage drop to 3% or less when supplying 120 amps for 200 feet on a 208 volt system.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What gauge wire for 208 volt 95 amp 200 ft?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What AWG cable for 200' x 208 volt three phase 250 amp circuit?

A wire size of 250 MCM will limit the voltage drop to 3% over a distance of 200 feet.


Transformer 208 volt primary and 480 volt secondary three phase 75 kva what size fuses on primar and secondary?

200 and 100


What is the wire size for 208 volt?

As with any electrical installation, the wire size used depends on the expected maximum current the wire will carry. That cannot be determined by voltage alone.


Does a 208 volt outlet need a neutral?

No a 208 volt outlet does not need a neutral. 208 volts is the line voltage between any two legs of a three phase 208 volt system.


What size breaker for a 208 volt single phase motor that pulls 1.4 amps?

208 volts is not a common single phase voltage but you could just size your breaker to the capabilities of the conductor. 208 is normally a phase to phase voltage <<>> Many 230 volt motors can be connected to lower voltage supplies. These motors can be connected to supplies of 208 and 200 volts. The code requirement is that the 230 volt full load amperage of the motor be increased by 10% and 15% respectively for wire sizing and breaker selection. To answer the question you will need a two pole 15 amp breaker.


What is the voltage value between one leg of a 208 volt system and the ground wire?

Well if you are talking about phases, it would be half of 208V.


What is 208 rounded to the nearest 100?

200


What size wire do you need for a 200 Amp 240 Volt 3 phase 4 wire service on a doctors office?

You might be out of luck. Three phase delta 240 volt services are a thing of the past. As far as I know there never was a 240 volt three phase four wire. The line to neutral voltage would be 240/1.73 = 139 volts which is of no use to anyone. Three phase four wire system for business and commercial use these days is 120/208 volts. A 3/0 copper conductor with an insulation factor of 90 degrees C is rated at 225 amps.


Why won't a 230-460 volt motor work on a 120-208 volt circuit?

Because its designed to operate at 230-460, not 120-208.


What happens when 240 volt equipment is plugged into a 208 volt source?

It should be ok


What is 200 million increased by 208 percent?

200 million increased by 208 percent = 616 million.


How will a 3 phase panel give you 110 volts and 220 volts?

A three phase panel will not give you 110 and 220 volts. A three phase four wire panel will, but not at these voltages. The nearest voltages will be 120 and 208 volts. The 120 volt is the wye voltage of 208 volts. 208/1.73 = 120 volts. A single phase three wire panel will give you 110 and 220 volts.