<<>>
A #3 copper wire with an insulation rating of 75 or 90 degrees C is rated at 100 and 110 amps consecutively.
In BC Canada, you need 2-#3 R90XLPE for the hot conductors, and 1-#6 R90XLPE for the neutral. Your ground is #6 bare copper.
A #3 copper wire with an insulation rating of 75 or 90 degrees C is rated at 100 and 110 amps respectively.
AWG # 4 copper.
SE #2
AWG #3
Service entrance wire should be AWG #3 copper.
At that distance you will have a voltage drop of 81.25 volts if you use the recommended #6 wire on a 240 volt, 100 amp single phase circuit. Therefore I recommend you contact you electric utility and let them figure the voltage drop and the size wire required to safely run this distance. Using too small a wire can damage the electronics at the end of the run.
The size of the wire is stated by its gauge under American Wire Gauge. Six gauge wire is size 6 AWG.
Wire size is governed by amperage not voltage. Voltage is an insulation factor when talking about wire. Add up the amperage of fixtures you want in the circuit. Once that is found then the size of the wire can be calculated.
Use what is called bell wire or thermostat wire.
Service entrance wire should be AWG #3 copper.
A #3 copper wire with an insulation rating of 75 or 90 degrees C is rated at 100 and 110 amps consecutively. As for the voltage, wire is usually rated in 300, 600 and 1000 volts. Any three of these insulations factors will handle 12 VDC.
A #3 copper conductor with an insulation factor of 90 degrees C is rated at 115 amps.
At that distance you will have a voltage drop of 81.25 volts if you use the recommended #6 wire on a 240 volt, 100 amp single phase circuit. Therefore I recommend you contact you electric utility and let them figure the voltage drop and the size wire required to safely run this distance. Using too small a wire can damage the electronics at the end of the run.
You can divide a three phase service into (3) single phase circuits providing you have a 4th neutral wire.
100amp
see American Wire Gauge. The larger the number the small the wire size.
Another 10 amp fuse. If you use anything larger, you can fry your equipment, cause a fire, and so on. If this fuse is blowing all the time, there is a short in the component or wire.
Wire size is the gauge (thickness of wire) hazard is almost anything not wired correctly.
The size of the wire is stated by its gauge under American Wire Gauge. Six gauge wire is size 6 AWG.
The insulation on a wire is applied after the wire is drawn to size.
10-32 unf-2a <<>> The wire size does not need to be calculated. Use a wire terminal end that crimps to the wire. These terminal end come in various wire sizes and bolt hole sizes. Pick the correct end for the wire size you are using and then in that wire size range, pick the correct bolt hole size that fits the bolt.