Best Answer

A 1/0 AWG aluminium conductor will limit the voltage drop to 3% or less when supplying 60 amps for 330 feet on a 240 volt system. The cable will be rated as ACWU 90. ACWU 90 cables are primarily intended for exposed and concealed wiring in dry or wet locations and where exposed to the weather. For use in ventilated, non-ventilated, and ladder type cable trays in wet and dry locations; direct earth burial; service entrance above or below ground.

User Avatar

Wiki User

8y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

12y ago

A #6 aluminum conductor with an insulation factor of 90 degrees C will limit the voltage drop to 3% or less when supplying 40 amps for 110 feet on a 240 volt system.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

A #6 aluminum conductor will limit the voltage drop to 3% or less when supplying 40 amps for 110 feet on a 240 volt system.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

A 2/0 aluminum conductor with an insulation factor of 90 degrees C will limit the voltage drop to 3% or less when supplying 125 amps for 120 feet on a 220 volt system.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size aluminum wire needed for 60 amp at 240 volt for 330 feet underground?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What size aluminum wire needed for 30 amp at 240 volt for 500 feet underground?

A 1/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 30 amps for 500 feet on a 240 volt system.


Thank you Is it possible to do the wiring in aluminum or is that old school?

Today the only use of aluminum wire is in service entrances and underground feeds where the larger sizes are needed. By using aluminum the overall project wire costs are kept to a minimum even with the bigger size needed over copper. Wiring branch circuit in aluminum has not been vogue for many years now.


What size underground service entry cable needed for 100 amp sub panel 600 feet from main?

AWG 2/0 copper.


What wire size needed for 150 amp service at 325 feet Copper or Aluminum?

This is a voltage drop question. To receive an answer to this question the voltage of the service must be stated.


What size aluminum ser cable needed for 100 amp sub panel?

#2 aluminum for 100 amp


What Is the wire size for 200 amp service running a distance of 200 feet?

Your service provider will give you that information The size will depend on: A) how close to the transformer are you. B) copper or aluminum C) Yes, you have a 400amp service but what will your actual peak amp usage be. D) Underground or overhead.


What size service underground wire for 60amp at60 feet?

# 6 copper wire.


What size conductors are needed to run a 400 foot residential underground electric service?

Need to know what size service is going to be installed at the end of the run.


How many cubic feet is in 1 pound of square aluminum tube?

1 cubic foot of aluminum weighs 169.344 Lbs


What size antenna is needed for a handheld aircraft radio?

3-4 feet long is ideal


What size conductors are needed to run a 650 foot residential underground electric service for a 200 amp service?

A 350 MCM copper conductor will limit the voltage drop to 3% or less when supplying 200 amps for 650 feet on a 240 volt system.


What size underground feeder wire is needed from a 400 amp breaker to a 125 amp panel box. The total distance is 100 feet?

1/0 <<>> This is a voltage drop question. A voltage and whether it is a single or three phase system must be provided to give an answer.