#8. It is better to error on the next large size. # 8 THHN 90 degree wire is rated at 45 amps. If there is a possibility that the breaker is connected to a 50 amp load the wire will be undersized. A #6 wire is rated at 65 amps. For continuous use, a load factor of 80% has to be applied. 65 x .8 = 52 amps. The only time the conductor can be smaller than the breaker size is on a motor feeder. Then the breaker is sized at 250% of the nameplate full load amps (FLA) rating of the motor. This is to allow the motor's starting current, which is about 300% FLA, to not trip the breaker on start up.
Depends on the wire size you are using. If the generator breaker is a 30 amp then install a 30 amp breaker.
Minimally 30 AMPS
The formula you are looking for is I = W/E.
50amp but if considering the breaker cannot withstand starting current you need to size the breaker up.
15, but I wonder if your information is correct. The breaker size doesn't seem to be right and a 240v circuit in a house uses a 2 pole breaker.
You need a 60 amp breaker.
Minimum size is 10 gauge with a 30 amp breaker. To be safe I would install an 8 gauge with a 40 amp breaker.
P=VI here P=8000 Watts v=220 V I=8000/220 = 37 A so you should use 37A Breaker
A miniature breaker is just two breaker that fit into one breaker slot. These types of breakers are designed to install the same as a full size breaker. Different types of breakers have different mounting configurations to the panels bus bars so installation instructions are not possible without knowing the make and type.
Assuming being fed by c32 breaker for start load minimum cable size SWA is 70mm which will go to 456 meters
Assuming you are referring to a 240 volt residential hot water heater you will need to install 10/2 NM cable (Romex) with ground from the service panel to the water heater wired to a 30 amp circuit breaker in the service panel. If you cannot see the water heater from the service panel you will need to install a service disconnect at the water heater.
6