Best Answer

If the service stack is supported by a support structure and the utility feed drop is not supported from the conduit, the size of the conduit can be 1 1/4". If the service stack is used to support the utility feed drop then the conduit has to be 2" schedule 40 conduit. The reasoning behind this is that if in a storm a tree limb falls across the service drop, the lighter weight conduit could bend and pinch the wires in the stack and short out. This would be ahead of the main service breaker and the only protection for the wire would be the primary fuse at the transformer. Theoretically this amperage could rise to 50000 amps before the primary fuse blows. A schedule 40 service stack if supported, as the code requires, will withstand most tree falls. What is most likely to happen is that the utility connectors will pull apart leaving the service stack intact.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

13y ago

Answer for USA, Canada and countries running a 60 Hz supply service.

Using THHN wire and EMT conduit, you need 1 inch for 3 conductor service or 1 1/4 inch for 4 or 5 conductor service. These are minimum size conduit and I recommend you not use the 1 inch regardless and use 1 1/2 inch conduit for a 5 conductor service.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

This answer is:
User Avatar

User Avatar

Wiki User

10y ago

A #3 copper conductor with an insulation rating of 90 degrees C is rated at 115 amps.

The minimum size conduit used on a 100 amp service is 1 and a 1/4 inches.

This answer is:
User Avatar

User Avatar

Wiki User

10y ago

AWG #3 wire

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

2''

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is the minimum size service cconduit for a 100 amp service?