Want this question answered?
For service sizes of 100 amps and less a #8 bare copper conductor is required.
A 100 amp service requires that you use AWG 4 copper wire or AWG 2 aluminum wire.
35 KVA generator using for load 100 meter length which cable need to used
A typical 100 amp service is comparable to a 25 KVA generator. That said, very few homes pull that much load. Most utilities size their distribution systems for a 5 KVA load per home, assuming that not all homes would pull full load at the same time. RPM is a function of the number of poles in the generator. To get 60 Hz power with a two pole generator, you need 1,800 RPM.
Approximate overall diameter of the wire is 12.8 mm. If you are looking for metric wire size 95 mm2. 187500 circular mils.
Volts * Amps = Watts 220V * 20 A = 4400 Watts BUT!!! You don't want to run a generator at 100% capacity for very long; that should be considered peak conditions only and the generator should be run at 80% or less. The generator will last a lot longer if you run it at 50% capacity (in other words, a generator with 8800 Watt capacity would be a good place to start)
For service sizes of 100 amps and less a #8 bare copper conductor is required.
A 100 amp service requires that you use AWG 4 copper wire or AWG 2 aluminum wire.
#2 Copper with TW insulation is required for 100 amp loads #3 Copper with R90 insulation is rated at 105 amps.
I would recommend you use AWG # 2 copper or AWG # 1/0 aluminum for that distance and amperage.
35 KVA generator using for load 100 meter length which cable need to used
A typical 100 amp service is comparable to a 25 KVA generator. That said, very few homes pull that much load. Most utilities size their distribution systems for a 5 KVA load per home, assuming that not all homes would pull full load at the same time. RPM is a function of the number of poles in the generator. To get 60 Hz power with a two pole generator, you need 1,800 RPM.
Approximate overall diameter of the wire is 12.8 mm. If you are looking for metric wire size 95 mm2. 187500 circular mils.
A 100 amp residential service requires a size #8 copper wire, it should be insulated in green.
Yes, an 8kVA generator can run a small house. A generator this size should be able to adequately power a one ton air conditioner, 18 cubic foot refrigerator, and other small appliances normally found in a small house.
20Sqmm
A #3 copper wire with an insulation factor of 75 and 90 degrees C is rated at 100 and 105 amps respectively.