What voltage?
The load is a little over 2kW, so the output needs to be rated no less than 2.5kW continuous (assuming the load is continuous).
--------------------------------------------------------------------------
The voltage is regulated by the number of field windings versus stator windings, multiplied by the voltage added to the field from a DC source. Phase factors and operating power factors will also affect the total kiloVolt-Ampere output of a generator. this is often factored in for household emergency generators and a generalized rating is given for a 220 volt output. for a 2049 watt load at 220 volts a single phase generator with with an output of 2500 watts or more should be used. The phase factor would be 1:1, power factor negligible (unless hooked to the power grid), and motor(generator) efficiency is about 96% typically. Adjusting for a 25% peak load (when items turn on and off) then:
(2049w/0.96)x1.25 = 2668 watts , a 2500 watt generator will handle it if not all things attached to it start at the same time.
This is equivalent to a 100amp circuit load at 220 volts or 200amps at 110 volts. (circuit breakers), most houses require a 200 or 300 amp service (add up all the circuit breakers in use in the box.)
note: single breakers are typically 110 volt and double breakers are typically 220 volts, when adding up breaker's amperage double the load for double breakers to compare the loading at 110 volts.
example:
Circuit box has 2 double (220v) breakers, stove/oven 30 amp, water heater 45amp, and 12 15 amp single breakers (110v) the total load for the service is:
(30 x 2)+(45 x 2) + (12 x 15) = 330 amps (@110 v) or 165 amp service (@220v)
165 amps x 220 volts = 33000 volt-amperes , because emergency generators are rated at 220 volts the kilowatt output needed is 1.65 x 125% = 206.25 kw @ 220 volts
For industrial generator ratings: volt-amperes = kilowatts x power factor x phase factor (3 phase generation phase factor is 1.732, power factor is adjusted by adjusting the field voltage) , these do not apply with emergency generators. {volts x amperes = watts}
ranch style home - 1500 square foot with partial basement. What size generator would be needed?
The cable that is used to connect from the generator is based on the size in kW's of the generator and the generator's breaker size rated in amps. It usually is a flexible cab-tire 4 wire cable if the generator is a portable type. If it is a stationary generator is has to be wired with a flexible conduit so as not to transmit vibration from the generator to the conduit system.
No, a 2800 watt generator is not large enough to run a home as stand by power. For a generator ot produce 100 amps a 25,000 watt or 25 kW generator would be needed. Since a house uses about 50 to 60 amp at any one moment during normal everyday living, a 60A x 240V = 14,000 watts. A 15 kW generator would be the minimum size generator to run a house without cutting back on any loads.
When you refer to a 200 amp welder you are talking about the output side of the welder. What you have to do is find out what the input voltage and current of the welder is to calculate the size of a generator needed to operate the welder.
A 1500 watt generator will do fine.
The size of diesel generator varies greatly. The size that is needed would depend on the size of the house.
The generator should be about ¾ hp.
ranch style home - 1500 square foot with partial basement. What size generator would be needed?
To answer this question the voltage and amperage of the unit must be stated. Once this is given the generator size can be calculated.
The cable that is used to connect from the generator is based on the size in kW's of the generator and the generator's breaker size rated in amps. It usually is a flexible cab-tire 4 wire cable if the generator is a portable type. If it is a stationary generator is has to be wired with a flexible conduit so as not to transmit vibration from the generator to the conduit system.
The size of the generator is based on the size of the load you want to supply. Size up the load in watts or amps along with what phase (single or three) and voltage that the load requires. These are needed to give a complete answer.
No, a 2800 watt generator is not large enough to run a home as stand by power. For a generator ot produce 100 amps a 25,000 watt or 25 kW generator would be needed. Since a house uses about 50 to 60 amp at any one moment during normal everyday living, a 60A x 240V = 14,000 watts. A 15 kW generator would be the minimum size generator to run a house without cutting back on any loads.
A generator for a three bedroom house would be medium sized. Try a small to medium sized generator that can be found online or at any hardware store in your neighborhood.
This depends on the size of the generator itself. The smaller the generator, the more RPM's will be needed to generate 200 volts in an A/C system.
The sizing of transformers is based on an accumulation of all of the loads that will be connected to it. Add up all of your loads and possible loads in the future and then tell your installer the figures and they will use these to calculate the size of the transformer that is needed.
To answer this question more information is needed. The wire size of the extention cord is needed.
A 5 kW generator would turn it over but if the full 30 hp of mechanical power is needed, that would require about 30 kW of electric power from the generator.