Best Answer

Answer for USA, Canada and countries running a 60 Hz supply service.

The wire size and breaker are determined by the amperage on the conductor used to feed the load. Amps = Watts/Volts. 2000/220 = 9 amps. The breaker used to feed this size load will be a two pole 15 amp breaker. A #14 two conductor cable is rated at 15 amps but has to be de-rated by 80% for continuous loads. 15 x .8 = 12 amps. This de-rating is still within the amperage you need to run the heater. There is in the market place now a two wire cable that uses red and black colour coding for electric heating. If you just have a cable with black and white colour coding identify the white wire by wrapping a piece of black tape on both ends around the wire to signify that the cable is used for 220 volts. This keeps the next person that opens the splice safe, as it tells the person that the white wire is not a neutral wire and that the wire is to be consider as a "hot" wire.

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

User Avatar

Wiki User

10y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size wire and circuit breaker for a 2000 watt 220 heater?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

Can I you use existing 8 3 wire hooked to a 30amp breaker was hooked to old electric heater to wire a heater that requires 10 2 wire its a 5000watt 240volt heater?

Yes the wire size is larger for that size breaker but will not effect the 30 amp breaker protection of that circuit.


When installing a circuit breaker do you size the breaker to correct wire size or the device its controlling?

When installing a circuit breaker, you size the breaker based on the wire size. The breaker should be matched to the ampacity of the wire to ensure proper protection against overloads and short circuits. The device being controlled by the breaker is not a determining factor in sizing the breaker.


What size wire and breaker do you need for a 5000 watt garage heater?

Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker


What size breaker and wire for 2000 watt heater?

A 2000 watt heater draws 8.3 amps on a 240 v supply, so the cutout should be set to 10 or 12 amps. <<>> In North America a 2000 watt baseboard heater will be fed with a two pole 15 amp breaker. A two wire cable of #14 copper will be used to connect the supply voltage to the heater.


What size amp circuit breaker should be used for a home entertainment system?

You use the correct size breaker depending on the size wire in the circuit. If the circuit is wired with AWG #12 wire use a 20 amp breaker. If it is wired with AWG #14 wire then use a 15 amp breaker.

Related questions

Can I you use existing 8 3 wire hooked to a 30amp breaker was hooked to old electric heater to wire a heater that requires 10 2 wire its a 5000watt 240volt heater?

Yes the wire size is larger for that size breaker but will not effect the 30 amp breaker protection of that circuit.


What size ext cord for 2000w heater?

Use #12 wire and a 20 amp two-pole circuit breaker.


When installing a circuit breaker do you size the breaker to correct wire size or the device its controlling?

When installing a circuit breaker, you size the breaker based on the wire size. The breaker should be matched to the ampacity of the wire to ensure proper protection against overloads and short circuits. The device being controlled by the breaker is not a determining factor in sizing the breaker.


What size wire and breaker do you need for a 5000 watt garage heater?

Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker


What size breaker and wire for 2000 watt heater?

A 2000 watt heater draws 8.3 amps on a 240 v supply, so the cutout should be set to 10 or 12 amps. <<>> In North America a 2000 watt baseboard heater will be fed with a two pole 15 amp breaker. A two wire cable of #14 copper will be used to connect the supply voltage to the heater.


What size amp circuit breaker should be used for a home entertainment system?

You use the correct size breaker depending on the size wire in the circuit. If the circuit is wired with AWG #12 wire use a 20 amp breaker. If it is wired with AWG #14 wire then use a 15 amp breaker.


How are Branch circuit protected?

Branch circuits are protected by the circuit breaker found in the electrical panel. Each circuit should have its one breaker. The breaker should be rated to protect the insulation of the wire, so you can determine the breaker size based on the circuit conductor size Example #14-2 should be protected by a 15 amp breaker


What size amp circuit breaker should be used for a hot water tank?

Assuming you are referring to a 240 volt residential hot water heater you will need to install 10/2 NM cable (Romex) with ground from the service panel to the water heater wired to a 30 amp circuit breaker in the service panel. If you cannot see the water heater from the service panel you will need to install a service disconnect at the water heater.


What is the standard to select circuit breaker?

Add up your amps to calculate your breaker size. Add up your loads (amps), divide by 0.8, and choose that size breaker. If that number does not correspond to a standard size breaker you go to the next higher standard size breaker.


Is the main circuit breaker is a sum of the sub circuit breaker?

Typically yes because that is what makes sense. However, the subpanel could have the same size breaker as long as the panel were rated for that amperage and the wire sizes were appropriate.


What is the smallest size circuit breaker found in the normal home?

The biggest circuit breaker in any home is the main breaker located in your main breaker panel that is installed where your electrical service cable comes into your home.


What size amp circuit breaker should be used for 110 outlet?

The size breaker you use is determined by the size wire used in the circuit. If you use AWG #12/2 wire then use a 20 amp breaker. If you use AWG # 14/2 then use a 15 amp breaker.