A breaker is sized by the load current. A breaker is used to protect the load feeder from an over current being applied to the conductor. If the load draws up to 30 amps, the wire size needs to be a #10 copper conductor or larger depending on the distance to the load with an insulation rating of 90 degrees C. The 460 volt source has to do with the insulation rating of the conductor. In this case the #10 conductor will need an insulation rating of 600 volts. Do not use 300 volt rated wire.
The rule of thumb is, 1mm sq will carry 6A, so for 30A use a 6mm sq cable
AWG #3 copper.
The size of conductor needed will be a #14. It should be copper and have an insulation factor of 90 degrees C. The fact that it is a three phase load does not enter into the calculation of the wire size.
A #8 AWG copper conductor with an insulation factor of 90 degrees C will limit the voltage drop to 2.26% or less when supplying 30 amps for 120 feet on a 220 volt system.
This is a voltage drop question. A 500 MCM copper or 750 MCM aluminium conductor will limit the voltage drop to 3% or less when supplying 300 amps for 500 feet on a 240 volt system. Paralleling these conductors will allow the rating to be increased to 600 amps.
A 10 mm cable is most commonly used for a 500 KVA transformer, 240 volt, 3 phrase. The size of the wire that is used in a transformer is based on the voltage.
AWG #3 copper.
The size of conductor needed will be a #14. It should be copper and have an insulation factor of 90 degrees C. The fact that it is a three phase load does not enter into the calculation of the wire size.
The electrical code states that a 7.5 HP 460 volt three phase motor draws 11 amps. For fuse sizes, non time delay - 30 amps, time delay type D - 20 amps and if using a breaker it will be 30 amps. Minimum wire size is #12 and the maximum setting of overload devices will be 13.75 amps
6 AWG
A 3/0 copper conductor with an insulation rating of 90 degrees C is rated at 225 amps.
10 AWG.
5000 volt
You might be out of luck. Three phase delta 240 volt services are a thing of the past. As far as I know there never was a 240 volt three phase four wire. The line to neutral voltage would be 240/1.73 = 139 volts which is of no use to anyone. Three phase four wire system for business and commercial use these days is 120/208 volts. A 3/0 copper conductor with an insulation factor of 90 degrees C is rated at 225 amps.
The electrical code book states that a 40 HP 230 volt three phase motor draws 104 amps. For that motor the wire must be rated for 131 amps, Non time delay fuses at 300 amps, time delay fuses at 175 amps or a 250 amp circuit breaker. When calculating wire sizes and motor protection the motor's full load amperage should be taken from the motor's nameplate.
Volts * Amps = Watts 12 V * ?Amps = 100 Watts OR ? Amps =100W/12V OR 8.33 Amps = 100W/12V Use a 10Amp fuse inline and you can get by with 16Ga wire.
A motor can be reckoned at 1.6 kVA per horse-power, so on a 415 v 3-phase suppy the current for 20 HP would be 45 amps. For continuous use the wire size should be 25 mm2
A #10 copper conductor will limit the voltage drop to 3% or less when supplying 21 amps for 150 feet on a 240 volt system.