If you put a 85 amp breaker in there it will overheat from the starting and stopping of the motor. The extra size of the breaker insures that the furnace will run without interruption and without overheating the breaker. And electric motor can draw three times the amperage rated on start up momentarily. This is why there is need of extra amperage ratings.
The equation for amperage is I = W/E, Amps = Watts/Volts. The amperage for the furnace would be, Amps = 15000/240 = 62.5 amps. So to answer the question, yes a 100 amp breaker with a #4 copper conductor will be sufficient to operate a 15 kW furnace. A 70 amp breaker will work but it is cutting the edge a bit too fine as you don't need the furnace to trip off during the winter months (northern hemisphere) if you are away from your home for an extended period of time.
The amperage capacity of the main bus bars and the connection of the main breaker to the bus bars.
A #3 copper conductor with an insulation factor of 90 degrees C is rated at 115 amps. Even though the panel is rated at a higher amperage it is the main breaker that governs the wire size.
It depends on what else you are running in the house. Add up your amperage to see if it is more than the 125amp rating. Which should be below 105 amps constant to keep from overheating the main breaker. If you are not running a big central ac system or a electric oven and water heater you should have no problem running the hot tub.
Usually 30 amp
Depends on the manufacture of the water furnace. Look at the data sheet or data plate on the furnace of contact the manufacture.
The equation for amperage is I = W/E, Amps = Watts/Volts. The amperage for the furnace would be, Amps = 15000/240 = 62.5 amps. So to answer the question, yes a 100 amp breaker with a #4 copper conductor will be sufficient to operate a 15 kW furnace. A 70 amp breaker will work but it is cutting the edge a bit too fine as you don't need the furnace to trip off during the winter months (northern hemisphere) if you are away from your home for an extended period of time.
No. If device draws 200 amps breaker will trip.
The amperage capacity of the main bus bars and the connection of the main breaker to the bus bars.
You need a 60 amp breaker.
A #3 copper conductor with an insulation factor of 90 degrees C is rated at 115 amps. Even though the panel is rated at a higher amperage it is the main breaker that governs the wire size.
by doing your mum
50 amp breaker.
No, they each need their own breaker of the right amp. Neither of them would cause the breaker to trip if there was a problem.
Yes. It should be a dedicated circuit from the distribution panel. There should also be an emergence shut off switch outside of the furnace area . This switch allows you to shut the furnace down from a remote area if a malfunction occurs at the furnace.
It depends on what else you are running in the house. Add up your amperage to see if it is more than the 125amp rating. Which should be below 105 amps constant to keep from overheating the main breaker. If you are not running a big central ac system or a electric oven and water heater you should have no problem running the hot tub.
Replace the 30 Amp Breaker with a 15 Amp breaker.