answersLogoWhite

0


Best Answer

No, that alone would not cause a GFCI to trip because that is the proper way to wire a panel.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Will a GFI outlet keep tripping because it's line is wired to a fuse box panel where the neutral and ground are together?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

Why no electric shock from neutral line?

There is normally no voltage on the neutral line because the neutral line is grounded. However, and this is always important, do not assume that neutral is grounded, nor that there is not an elevated voltage on neutral or ground due to a possible ground fault.


Why isn't there a ground in a junction box?

Only the main panel is grounded directly because if you ground each junction box of subpanel ground loop current paths are possible that can cause shock hazards. The ground rod is connected to main panel and the neutral is bonded to that ground as is the ground wire. The neutral and ground wire are then run to all circuits, junction boxes and subpanels throughout the house. If you tie neutral and ground together at any point in the house, other than the main panel ground loops can exist and cause shocks.


What is meant by neutral grounding reactor?

Neutral-earthing reactors or Neutral grounding reactors are connected between the neutral of a power system and earth to limit the line-to-earth current to a desired value under system earth fault conditions.


What are white black and green colors represent on electrical wires?

In the US, the common usage of these colors is: BLACK: Hot - connected to one phase of the service AC. WHITE: Connected to the Neutral of the service AC. GREEN: Connected to the GROUND bus at the service entrance. At the service entrance, the GROUND and the NEUTRAL bus are connected together.


How do I rewire an ungrounded plug?

If there is no ground wire connect the ground wire to the neutral wire.

Related questions

Why are the GFCI breakers nuisance tripping in your 100 amp sub panel- is it because neutral bonded to ground?

It may be the GFCI breaker is defective. Make sure it is wired correctly. Neutral to neutral bar and ground to ground bar.


Why would your pool circuit breaker go off?

Probably because you are either drawing too much current or you have a ground fault. If your ground fault breaker is tripping, or if you have a ground fault receptacle is tripping then you have too much circulating current through your neutral. There are many factors to consider there. Provide more information about what is on the pool's circuit and we can explore the options.


Why do some electric panel have ground and neutral bonded together?

By National Electric Code only the Main Panel should bond ground and neutral. If subpanels have ground and neutral bonded, it could cause ground loops and shock hazards.


What happens if you wire a ground and neutral wire together in an outlet box?

If there is a GFCI in the circuit it will stop working correctly. They compare ground current to neutral current to detect a fault. It makes ground current equal to neutral current which is a fault condition.


Where are neutral and ground wires usually bonded together?

Only in the main electric panel.


In the electrical system of the US what is the difference between the neutral and the PE Ground?

US NEC: The neutral conductor is an insulated grounded conductor used as the current return in a circuit. The color designation for neutral is white. The protective ground (PE, protective - earth) is a non-insultated grounding conductor used to shunt fault current to ground, tripping the protective device. The color designation for PE ground is green. Neutral and PE ground are tied together at the distribution panel. PE ground is also connected to a solid earth ground, such as grounding rods driven into the earth. Downstream of the distribution panel, PE ground is never used to carry operational current. Any current flow on PE Ground, other than parasitic current, is considered a ground fault, which must be corrected. In fact, GFCI (Ground Fault Current Interrupting) breakers will trip when neutral current does not match hot current, an indication of PE ground current flow.


Why no electric shock from neutral line?

There is normally no voltage on the neutral line because the neutral line is grounded. However, and this is always important, do not assume that neutral is grounded, nor that there is not an elevated voltage on neutral or ground due to a possible ground fault.


Why isn't there a ground in a junction box?

Only the main panel is grounded directly because if you ground each junction box of subpanel ground loop current paths are possible that can cause shock hazards. The ground rod is connected to main panel and the neutral is bonded to that ground as is the ground wire. The neutral and ground wire are then run to all circuits, junction boxes and subpanels throughout the house. If you tie neutral and ground together at any point in the house, other than the main panel ground loops can exist and cause shocks.


Why we don't get shock if we touch neutral wire..we need two wires to close circuit pH and n when circuit closes current will flow around the circuit and one wire gets shocked other not why?

We don't get shocked when we touch neutral and ground because neutral is grounded back at the distribution panel, so the effective voltage between neutral and ground is very low. It won't be zero, because there is current flowing on neutral, causing a voltage difference between the load and the distribution panel, but it is low enough, assuming there is no malfunction, to not cause a shock.In the case of touching hot and neutral, or hot and ground, you will get shocked because there is line voltage between hot and neutral, and because neutral and ground are connected together, there is also line voltage between hot and ground.Note, however, that connecting a load between hot and ground is a violation of the code and the intent of the design, because ground is not rated to carry current except in short term fault conditions - you must always connect a load between hot and neutral, or between hot and hot, as the case may be.


What is symptom of a circuit incorrectly wired?

Circuit breaker tripping, or non functioning outlet. The neutral and hot can be reversed, or an open ground, and you will have no symptoms. This can only be detected with a circuit tester you plug in to check the wiring.


Why is residential wiring called single phase if there are 2 phases coming in?

residential wiring are called single phase because the 2 phases coming in are one is neutral and the other is line.the neutral has a potential zero with ground and it is to provide a closed path for the current to flow through..the line is having a potential of 230V with the ground and a line together with a neutral is called a phase


Can you tackle a runner by tripping?

Not sure exactly what you're asking, but yes, you can knock a runner over by tripping into them. All it really takes is a hard shove, because a runner's feet rarely touch the ground at the same time.