It shouldn't. Check the nameplate for input amperage of the machine. Your #6 wire is good for 60 amps. If the nameplate amperage is below 60 amps then you are good to go.

User Avatar

Wiki User

15y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Would using a 60 foot extension cord which is 6 gauge 3 wire cord on a 220 volt single phase welder present any problems?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Would using a 200 foot extension cord which is 6 gauge 3 wire cord on a 220 single phase welder present any problems?

Absolutely, you will have voltage drop, maybe enough voltage drop that the welder will not work <<>> To do a voltage drop calculation for the 200 foot cable the input amperage of the welder needs to be stated. At a maximum distance of 201 feet and limiting the voltage drop to 3% or less, a #6 copper conductor can deliver 37 amps on a 220 volt system. Check the nameplate on the welder to see if it falls withing the range of 37 amps input amperage. Do not use the welders output amperage.


What does the term single hand welder mean?

A "single hand welder" is any person welding on a job that is not using their own personal equipment. I.E., welding with a company welder or rented welder until you can afford to buy your own welder.


What is a good present for a dad who welds?

google " gifts for the welder"


What is the best size wire for a welder extension cord?

25 percent larger wire for 50 feet.


What is the 60 Hz on a welder with the listed input as 208 230 volt single phase 60Hz?

60 Hertz is the frequency that the welder should be connected to, to work as it is designed to.


If you have a spa that is 240V with 4 wires can you hook an extension cord from a 240V welder to it to see if it works if the cord only has three wires?

Well, maybe. What is the current rating on the spa circuit? What is the current rating on the welder? If the welder is larger than the outlet, then no. It must be the other way around. If the current ratings are OK, then yes. Your welder doesn't need 110V so it doesn't connext to neutral. Connect the hot leads to hot and ground to ground.


What is the pay rate for experieced welder in NJ?

What is the yearly wage of a welder? What is the yearly wage of a welder? What is the yearly wage of a welder?


Can a welder be promoted?

Pipe welder?


Is TIG Welder is also considered as Co2 welder?

No , although Co2 may be used , along with other gasses , a welder using this process is not considered a Co2 welder . TIG stands for tungsten Inert Gas , so the welder is considered / called a TIG Welder.


How big of a generator do you need to drive a 200 amp welder?

When you refer to a 200 amp welder you are talking about the output side of the welder. What you have to do is find out what the input voltage and current of the welder is to calculate the size of a generator needed to operate the welder.


What size wire for a welding extension cord 220v 50 amps?

Wire size depends on amps. Use #10 for 30a. #8 for 40 or 50a. #6 for 60a.