Fuses, Circuit Breakers, GFCI (Ground Fault Circuit Interrupter), Surge Protector, etc.
Not if the GFCI breaker is supplying the circuit you are wanting to put the GFCI receptacle into.
A GFCI outlet has a TEST and RESET switch. Press reset and see if it fixes problem. If reset won't stay in that means that a ground fault condition is present and may be on another outlet that is fed from the tripped GFCI. If this isn't the problem check the main breaker feeding the GFCI and ensure it isn't tripped. If none of this works the GFCI itself may be bad. If you have a Volt Meter you can remove the outlet from the wall receptacle and make sure there is voltage present. You can also see if there is a branch circuit connected. To troubleshoot you can disconnect the branch circuit and then try reset. If you have voltage on input and GFCI won't reset with branch circuits removed, replace the GFCI.
Your question is a bit vague, but let's try a two part answer. If you have a GFCI breaker in an electric panel you should only have one connection at the breaker, but the breaker will protect all devices on the circuit. If you are talking about a GFCI outlet, they are equipped to extend the GFCI protection to other non-GFCI outlets by using the proper "output" connection on the GFCI.
Deoends on code you are governed by. In USA, a GFCI outlet or a circuit controlled by a GFCI circuit breaker would be required.