Wiki User
∙ 11y agoNo; drawing more than the rated amperage from a transformer will cause it to overheat.
Wiki User
∙ 11y agoa 220 volt, 3200 watt oven will draw under 15 amps, so yes a 2o amp breaker will work.
A 30 amp breaker run 75 feet would require you use AWG #10 wire. But, an oven normally pulls more that 30 amps and I would not use #10 wire on a 30 amp breaker for an oven. Normally any newer oven is wired with AWG #6 gauge wire on a 50 amp circuit breaker so the breaker will not trip during heavy use of the oven. Some older ovens could use a #8 wire on a 40 amp breaker.
Amps * Volts = Watts Amps * 12 = 600 600/12 = Amps = 50 amps You would need a reserve capacity, so I'd go somewhere between 60 or 100 Amp rated transformer. Transformers are rated in volt-amps which is usually calculated the same as watts. But the term "watts" technically does not apply to transformers. So you need a 600 volt-amp transformer or, as Redbeard has suggested, you need an 800 or 1000 volt-amp transformer. That's a lot of amps for a 12 volt system so I recommend you double check your requirements. You will need a #2 gauge wire if your requirements are correct.
Yes it can if it's connected in a push pull reconfiguration
A 60VA transformer can run only one 50W bulb.
no
a 220 volt, 3200 watt oven will draw under 15 amps, so yes a 2o amp breaker will work.
A 30 amp breaker run 75 feet would require you use AWG #10 wire. But, an oven normally pulls more that 30 amps and I would not use #10 wire on a 30 amp breaker for an oven. Normally any newer oven is wired with AWG #6 gauge wire on a 50 amp circuit breaker so the breaker will not trip during heavy use of the oven. Some older ovens could use a #8 wire on a 40 amp breaker.
10kw
The short answer is no. The long answer is no, not if you are using standard 100-120 volt or 220-240volts found in most (all?) countries The following is a simplified best case scenario, which incorrectly assumes a power factor of 1. Power = Volts * Amps Watts = Volts * AMPS (Actually VA = Volts * Amps, but VA=Watts in best case scenario) but 10kw > 240 * 32. David
Normally older ovens required a AWG #8 wire on a 40 amp breaker. On a modern double oven I would recommend you install AWG #6 on a 50 amp breaker. That way you are safe and will not have to worry about the breaker tripping. It will cost a little more but is worth it in the long run.
Amps * Volts = Watts Amps * 12 = 600 600/12 = Amps = 50 amps You would need a reserve capacity, so I'd go somewhere between 60 or 100 Amp rated transformer. Transformers are rated in volt-amps which is usually calculated the same as watts. But the term "watts" technically does not apply to transformers. So you need a 600 volt-amp transformer or, as Redbeard has suggested, you need an 800 or 1000 volt-amp transformer. That's a lot of amps for a 12 volt system so I recommend you double check your requirements. You will need a #2 gauge wire if your requirements are correct.
Yes it can if it's connected in a push pull reconfiguration
A 60VA transformer can run only one 50W bulb.
I have, I have even used the output for the input of the same amp, so that you only run one RCA cable to the amp, then run the output back to the other input, and it runs 4 channels.. :o)
If you want to run both coils,you have to wire the positive to positive and negative to negative on your sub,then run a wire from each plug to the amp. Positive to the positive side of the amp and negative to negative side of the amp,(you can run in bridge mode or stereo if your amp can handle the load)
To run a monitor speaker or to connect several amps in series to pre-amp your amp.