answersLogoWhite

0

n you run thhn wire in a cable tray

User Avatar

Wiki User

11y ago

Still curious? Ask our experts.

Chat with our AI personalities

ProfessorProfessor
I will give you the most educated answer.
Chat with Professor
JudyJudy
Simplicity is my specialty.
Chat with Judy
TaigaTaiga
Every great hero faces trials, and you—yes, YOU—are no exception!
Chat with Taiga

Add your answer:

Earn +20 pts
Q: Can you run thhn conductors exposed?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

What is the ampacity of each five no 8 aluminum conductors with thhn insulation being routed through a conduit with ambient temperature of 75 Celsius?

School question. The answer can be found in your electrical code book.


Can a three phase circuit be installed in the same conduit or in different conduits?

The conductors of any three phase circuit must be run in the same conduit. If the circuit requires a neutral, it must also run with the conductors in the same conduit. (If they were to be run in more than one conduit or raceway, the circuit would not operate properly.)


What size conductors are needed to run a 400 foot residential underground electric service?

Need to know what size service is going to be installed at the end of the run.


Does the Nec allow grounding electrode conductor to be run in conduit that has other conductors in the conduit and what code section?

No, the bare copper grounding conductor can not be in a conduit with other conductors. It can be in conduit by itself to provide mechanical protection for the wire.


What does an underground electrical pull box do?

An underground electrical pull box provides another access point in long runs of cable to make it easier to pull the conductors from one end of the run to the other. The crew can only slap so much silicone lube on the conductors and the the conductors can only have a limited amount of force applied on them to pull them through the conduit. If a long run is broken up somewhere in the middle, the crew can pull to that point where the pull box is located, and then "start a new pull" from the box to the end of the run. It's more work, but it protects the conductors and the job ends up "meeting code" and passing inspection.