No. You aren't allowed to install a device rated greater than the circuit is rated.
The 20 amp receptacle would allow you to plug in 20 amp loads (which is why it is different than a 15 amp receptacle), and plugging a 20 amp load into a 15 amp circuit would cause an overload and the 15 amp circuit breaker would trip.
ADDITION
This may still be open for discussion. According an electrician from RKO Electric, you can in fact install a 20 Amp GFCI receptacle on a 15 Amp breaker. Apparently, the breaker will trip well before the receptacle is able to pull 20 Amps of current into the line. Please see the following link from another website: http://en.allexperts.com/q/Electrical-Wiring-Home-1734/20-amp-GFCI-outlets.htm
2003 NEC Code Book says:
210-21(b)(1), p.70-42: A single receptacle on an individual branch circuit shall have an ampere rating of not less than that of the branch circuit. To me this indicates that if there's only one receptacle on the circuit, you can't have an outlet rated for less than the circuit, but it neither mentions nor prohibits oversizing the receptacle.
210-21(3), p.70-42: Where connected to a branch circuit supplying two or more receptacles or outlets, receptacle ratings shall conform to the values listed in table 210-21(b)(3)... which says: 15amp circuit, not over15amp receptacle (=15amps); 20amp circuit, 15 or20amp receptacle. In contrast to (b)(1) abopve, in the case of 2 or more receptacles on the same 15 or 20amp circuit, this now seems to place the restriction on the other end of the scale. Now it does limit how large the receptacle can be rated, while also setting the boundary for how small.
If it is a 32-amp circuit you can use any appliance that takes less than 32 amps. That includes a 15-amp appliance. All appliances fed from that circuit must use 32 amps or less in total.
Answer for UK, Europe and countries running a 50 Hz supply service.A ring circuit has two routes to each outlet, a radial has only one.
The size breaker you use is determined by the size wire used in the circuit. If you use AWG #12/2 wire then use a 20 amp breaker. If you use AWG # 14/2 then use a 15 amp breaker.
No. A 20 amp breaker needs 12 gauge wire.
Every outlet in a home or a school is in parallel with every other outlet in the same home or school, and also very possibly with every outlet in several other buildings nearby. Every time you plug something into an outlet, you're connecting that thing in parallel with every other electrical thing that's plugged into any of those others.
# 6 wire
Yes, you can use a 15 amp outlet on a 20 amp circuit. The outlet's amp rating should not exceed the circuit's amp rating.
A 20 amp circuit with #12 gauge wire will work in any event but if the nameplate recommends a 15 amp circuit then #14 gauge wire on a 15 amp circuit is sufficient. In either case you will have a double pole breaker and your equipment may not require a neutral. Always run a grounding conductor.
Wall outlets in the bedroom can be on a 15amp breaker as long as they are not part of a dedicated circuit that may have higher power demands. Typically, 15amp breakers are standard for general outlets in residential bedrooms.
No, it is not safe to use a 20 amp outlet on a 15 amp circuit as it can overload the circuit and potentially cause a fire hazard. It is important to match the outlet with the circuit's amp rating to ensure safety.
No, it is not recommended to use a 15 amp outlet on a 20 amp circuit as it may lead to potential safety hazards. It is best to match the outlet amperage with the circuit amperage for proper functionality and safety.
No, it is not safe to use a 15 amp outlet on a 20 amp circuit as it can lead to overheating and potential fire hazards. It is important to match the outlet's amp rating with the circuit's amp rating for safety reasons.
No, a GFCI outlet is designed for use with standard 120-volt circuits. Attempting to use a GFCI outlet with a 240-volt split circuit could cause damage to the outlet, the circuit, and could present a safety hazard. It is not recommended to use a GFCI outlet in this manner.
If it is a 32-amp circuit you can use any appliance that takes less than 32 amps. That includes a 15-amp appliance. All appliances fed from that circuit must use 32 amps or less in total.
If you are talking about a plug rated at 20 A and not that the device it is attached to as drawing 20 A then nothing will happen unless the device along with other devices on the same circuit trip the breaker. The rating of 20 A on a plug tells you the maximum current that should go through the plug. The 15 A breaker protecting the outlet ensures that no more than 15 A can go through your 20A plug.
The fuse is there to protect the wiring in your home not the microwave. Using a larger fuse than required for the wiring causes a fire hazard. You can end up burning your home down. Use only the fuse recommended.
No, it is not safe to use two 20 amp circuit breakers to protect a 40 amp circuit. Circuit breakers are designed to protect the wiring in a circuit from overheating, and using a higher amperage circuit breaker than the wiring is rated for can lead to overheating and potential fire hazards. It is important to use the correct size circuit breaker for the amperage rating of the circuit.