Need to know the wire # size to compute wire fill in conduits
ONE
In the electrical industry there are many different types of sleeves used. There are insulation sleeves, linesman's high voltage sleeves and conduit sleeves to name a few. The insulation sleeve is used for the protection of electrical conductors. Linesman's sleeves are used for extensions to the protective rubber gauntlets that they wear when working on high tension wiring systems. Conduit sleeves are used when a broken conduit needs to be repaired in situ.
53
There has to be a pull box between every four quarter bends in a conduit run.
Oh, dude, the space factor is crucial for conduits because it determines how many conductors can fit inside without causing a traffic jam of wires. It's like trying to cram too many people into an elevator – not a good idea. So, you gotta make sure you have enough space for all those wires to hang out comfortably and do their thing without getting all tangled up.
9
Stranded conductors are made up of many smaller solid conductors. In order to bunch the solid conductors to make the stranded wire they have to be held together. The simplest way of doing this is to twist them together. Once the solid wires are twisted together they are drawn through a machine that applies the insulation coating which holds the solid wires together. The final result is a insulated stranded conductor that has good flexibility. With this flexibility multiple stranded conductors can be easily be drawn through conduit systems that incorporate up to four 90 degree bends between junction boxes.
According to the 2005 NEC Annex C, table C.1 you are allowed nine #12 THHN conductors in a 1/2" trade size EMT conduit. If your conduit run is any length at all, you would be wise to increase the conduit size to 3/4". as pulling 9 #12's for any length in 1/2" EMT is very difficult.
ONE
16 current carry conductors
The simple answer to your question is yes. But there are limits to how many wires can be in any conduit, and the current carrying capacity of the conductors can be affected by distance, ambient temperature, and how many conductors are contained in the same conduit. Other things to consider are, Can you physically fit the wires in there? Would it be easier to run a new conduit? Do you have the manpower necessary to get the work done?
14
11
10
4
6 nches
6