To answer this question the voltage of the generator must be given.
Chat with our AI personalities
To answer this question the voltage of the generator must be given. That is because for each phase the kVA figure is equal to the line-neutral kV times the amps.
106 amps
If your generator is rated at 1000 watts continuous......and you are using 120V.....available amps are 1000/120 =8.3 .
At 240v single phase it's 70.8 amps. If it runs on 2 wires plus ground, take the voltage rating of the equipment and divide that into the watts to get amps. At 480v 3 phase it's 25.8 amps. At 208v 3 phase it's 47.2 amps. <<>> There are zero amps in 14 kW. A voltage needs to be stated. I = W/E, Amps = Watts/Volts.
There is not enough information provided to answer. KVA is short for "Kilo Volt Amperes". That is, thousands of Volt Amps. In order to determine how many Amperes are flowing, you must know at what voltage it is operating. Amperes = 45,000 ÷ volts Bill Slugg
36.6 amps maximum at 120 volts, but should not be loaded to over 29 amps. At 240 volts it will produce a maximum of 18.3 amps but never loaded to any more than 14.6 amps.