because y phase is y phase ...it is not b phase or R phase so it is high
It is very simple. Just interchange any two phase wires. i.e. Y and B ( or ) R and B ( or ) R and Y for example Stop the supply. keep R phase wire as it is and disconnect B phase wire and Y phase wire. Connect B phase wire to the Y phase motor stud and Y phase wire to the B phase motor stud. Now give the supply, now motor revolves in opposite direction to the earlier.
R - Red Y - Yellow B - Blue
It's just that, 3 phase, Y. It's typically used in large businesses and manufacturing facilities.
Postcode for Kidderminster in the West Midlands, UK. Also a vector group (connection configuration) of a 3-phase transformer.D - Means Delta Wound Primary Y - Means Wye (Star) Wound Secondary 11 - Is the phase shift between the two windings. The 11 refers to 11 on a clock face, hence 30 degrees.
408 volts x 1.73 = 277 volts is the star ( Y ) point of 3 phase 480V. A transformer connected in a Delta configuration is different than a Y or Star configuration. 277 volts is a voltage that is used in industrial plants usually for lighting. The following link will explain the whole star delta connection. http://www.allaboutcircuits.com/vol_2/chpt_10/6.html
A Y current is the electric current through one branch of the star arrangement of a three-phase circuit.
Y-delta transformations are used in electrical engineering to convert circuits from a Y configuration to a delta configuration or vice versa. This conversion simplifies analysis and calculations for circuits with complex interconnections by reducing the number of elements to consider. It is commonly used in power distribution systems and control systems to optimize system performance and efficiency.
For a 225 amp 208 volt 3 phase circuit, you would typically need to use a 3/0 AWG copper wire or a 250 kcmil aluminum wire. Be sure to consult with local electrical codes and regulations to ensure compliance with specific requirements for your installation.
In a star configuration, often called "Y", the voltage across one winding is from a phase to ground. Phase to phase you have voltage across 2 windings. And at the risk of confusing you, the phase to phase voltage is not double the other because the windings are only 120 degrees out of phase and not 180 degrees. To calculate this you take the voltage of one winding, 120v for example, and multiply by the square root of 3, or about 1.732, and get 208v. Or you take 277v and get 480v.
A three phase alternator (sometimes incorrectly called a generator or AC generator) is a device that changes rotational mechanical energy into electrical energy. The power grid transmits three phase electrical power (usually in Delta configuration) from electricity suppliers to local distribution systems; which then distributes the electrical power as either three phase Delta configuration, three phase Y configuration, two phase, or single phase power depending on the needs if the users.
because y phase is y phase ...it is not b phase or R phase so it is high
If one of the phases continuously takes a high load with a poor power factor it might have tripped a circuit breaker in the capacitor bank.
Currently, in popular usage, 3 phase systems are arranged in a "Y" or "star" configuration with the same voltage from each leg to ground. Primary sides of transformers are in a delta, "triangle", configuration but this is not the utilized side. In some old systems, the utilized system is delta with the mid point of one winding grounded. The phases at each end of this winding will measure half the volts to ground as from phase to phase. The phase farthest from the grounded winding measures a much higher voltage to ground than phase to phase since, in simple terms, it is measuring the voltage across 1 and 1/2 windings.
208 volts is the phase to phase voltage on a three phase low voltage system. In a split single phase service, the voltage is 120/240. In a three phase service, the voltage is 120/208. This is due to using a different transformer configuration. In the above, the first number is the phase to neutral reading, and the second is the phase to phase reading. For example, 120/240 and 120/208 both provide 120v on standard receptacles, but when using a dryer, or hot water heater, for example, that appliance would be using 240v or 208v, respectively.
The trivalent ion with the electron configuration of Kr 4d^3 is the Yttrium (Y^3+) ion. Yttrium differs from krypton (Kr) by losing three electrons to achieve the electron configuration of Kr 4d^3.
NO however id uyou use thirtyeen you can gt high (y)