This is a voltage drop question. A #1 copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 200 feet on a 240 volt system. Or

a 3/0 copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 200 feet on a 120 volt system. In your question you sis not stipulate what the working voltage is.

User Avatar

Wiki User

13y ago

What else can I help you with?

Continue Learning about Electrical Engineering

What gauge Aluminum underground wire will you need to install a 50 amp service in a outbuilding - 215 feet?

I would use AWG #4 for that run in alluminum. You will have a 3.8% voltage drop which is acceptible.


What size wire do you need to run overhead to a 50 amp service five hundred feet away?

For that distance I would run AWG # 3 copper and install a sub-panel.


What is the correct pipe size for a service entrance to a house?

The correct pipe size for a service entrance to a house typically depends on the electrical load and local building codes. For residential service, a common size is 1 inch for a 100-amp service and 1.25 inches for a 200-amp service. It's essential to consult the National Electrical Code (NEC) and local regulations to ensure compliance and proper sizing based on the specific requirements of the installation. Always consider factors like distance from the service panel and the type of conductors used.


What size conductors are needed to run a 400 foot residential underground electric service?

Need to know what size service is going to be installed at the end of the run.


What is the cable between the service panel and electric meter called?

Whether you have an overhead or underground feed, that section of the installation is referred to as Service Entrance Conductors. On an overhead installation, it includes the conductors on BOTH sides of the meter, from the service drop conductors (attached at the service head) to the service equipment LINE terminals. On an underground installation, it refers only to the conductors between the meter's LOAD side and the service equipment LINE terminals. The conductors on the LINE side of the meter come from a distribution transformer and are unbroken between the transformer and your meter.

Related Questions

When was Weather Underground - weather service - created?

Weather Underground - weather service - was created in 1995.


How can I install a mailbox at my residence?

To install a mailbox at your residence, follow these steps: Choose a location that meets postal service regulations. Dig a hole for the post, ensuring it is secure and upright. Attach the mailbox to the post according to manufacturer instructions. Secure the post in the hole with concrete or gravel. Make sure the mailbox is at the correct height and distance from the road. Notify the postal service of your new mailbox location.


What gauge Aluminum underground wire will you need to install a 50 amp service in a outbuilding - 215 feet?

I would use AWG #4 for that run in alluminum. You will have a 3.8% voltage drop which is acceptible.


What gauge Aluminum underground wire will you need to install a 50 amp service in a outbuilding 215 feet?

I would use AWG #4 for that run in alluminum. You will have a 3.8% voltage drop which is acceptible.


How to install a mailbox properly?

To install a mailbox properly, first choose a location that meets postal service regulations. Dig a hole for the post, ensuring it is secure and level. Place the post in the hole and fill it with concrete. Attach the mailbox securely to the post according to the manufacturer's instructions. Finally, make sure the mailbox is at the correct height and distance from the road for postal workers to access easily.


What Is the wire size for 200 amp service running a distance of 200 feet?

Your service provider will give you that information The size will depend on: A) how close to the transformer are you. B) copper or aluminum C) Yes, you have a 400amp service but what will your actual peak amp usage be. D) Underground or overhead.


What size underground wire is recommended for a 200 amp service?

For a 200 amp service, it is recommended to use a size 2/0 or larger underground wire.


National Park Service on the underground railroad?

why does no one have a answer


What literature about the Underground Railroad has the park service published?

i have no answer for this


What do you call electricity which comes to your homes?

The connection is known as a service drop. There are two types of service drops, an overhead connection to the house is known as a service dip and an underground connection to the house is known as an underground installation.


What was the first major finding in the underground railroad?

why did congress direct the national park service to study the underground railroad


Correct the grammar - service has assessed or the service have assessed?

service has assessed