This is a voltage drop question. A #1 copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 200 feet on a 240 volt system. Or
a 3/0 copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 200 feet on a 120 volt system. In your question you sis not stipulate what the working voltage is.
I would use AWG #4 for that run in alluminum. You will have a 3.8% voltage drop which is acceptible.
For that distance I would run AWG # 3 copper and install a sub-panel.
Need to know what size service is going to be installed at the end of the run.
Whether you have an overhead or underground feed, that section of the installation is referred to as Service Entrance Conductors. On an overhead installation, it includes the conductors on BOTH sides of the meter, from the service drop conductors (attached at the service head) to the service equipment LINE terminals. On an underground installation, it refers only to the conductors between the meter's LOAD side and the service equipment LINE terminals. The conductors on the LINE side of the meter come from a distribution transformer and are unbroken between the transformer and your meter.
How do i install aluminum bonding strap in sub panel of 100 amp service
Weather Underground - weather service - was created in 1995.
To install a mailbox at your residence, follow these steps: Choose a location that meets postal service regulations. Dig a hole for the post, ensuring it is secure and upright. Attach the mailbox to the post according to manufacturer instructions. Secure the post in the hole with concrete or gravel. Make sure the mailbox is at the correct height and distance from the road. Notify the postal service of your new mailbox location.
I would use AWG #4 for that run in alluminum. You will have a 3.8% voltage drop which is acceptible.
I would use AWG #4 for that run in alluminum. You will have a 3.8% voltage drop which is acceptible.
To install a mailbox properly, first choose a location that meets postal service regulations. Dig a hole for the post, ensuring it is secure and level. Place the post in the hole and fill it with concrete. Attach the mailbox securely to the post according to the manufacturer's instructions. Finally, make sure the mailbox is at the correct height and distance from the road for postal workers to access easily.
Your service provider will give you that information The size will depend on: A) how close to the transformer are you. B) copper or aluminum C) Yes, you have a 400amp service but what will your actual peak amp usage be. D) Underground or overhead.
For a 200 amp service, it is recommended to use a size 2/0 or larger underground wire.