answersLogoWhite

0


Best Answer

Wire sizing of a feed conductor is based on the amperage that a device draws. To calculate amperage from KVA a voltage of the supply has to be stated. Without this voltage and whether the transformer is single or three phase an answer can not be given.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size wire 100 kva transformer?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What size of cable wire used for 500 kva transformer 240 volt 3 phase?

A 10 mm cable is most commonly used for a 500 KVA transformer, 240 volt, 3 phrase. The size of the wire that is used in a transformer is based on the voltage.


What is the xlpe for a 34.5kv?

How to compute for the size of wire in the primary side of 2500 kVA transformer 34.5kV


What size ground wire for a 30 kva transformer?

The size of grounding wire is based on the amperage output of the transformer. The voltage of the transformer needs to be stated. Without this voltage a calculation can not be made. Amps = Watts/Volts = 30000/?.


Transformer 208 volt primary and 480 volt secondary three phase 75 kva what size fuses on primar and secondary?

200 and 100


What is the difference between a 1.5KVA and a 3KVA transformer?

The 3 kVA transformer will weigh double the 1.5 kVA transformer.


What is the kw of 100kva transformer and how you calculate?

The kW rating of a transformer can be calculated by multiplying the kVA rating by the power factor. For example, if the power factor is 0.8, then the kW rating of a 100 kVA transformer would be 80 kW. You can also use the formula: kW = kVA x power factor.


How do you earth in the 1600 kva transformer?

In 1600 kva transformer we provide NGR (Neutral grounding resistance)


What is the KVA rating required of the testing transformer?

Depends on the kva rating of the devices to be tested using a transformer.


Why the transformer rating in kva why not in kw?

A transformer has separate ratings for maximum voltage and maximum current. Both limits must be observed. The maximum voltage is set by the magnetic flux density in the core, while the current limit is set by the size of the wire used in the primary and secondary windings. Multiplying the two together gives the VA or kVA rating.


Why you are indicating capacity of transformer in KVA?

transformer action doesn't depend on power factor that is why we indicate its rating in KVA


How do you compute for the size of wire in primary side of transformer 34.5kv?

There is insufficient information in the question to properly answer it. While you specified the primary voltage, 34.5 Kv, you did not specify the current or the KVa. Please restate the question.


What is the result when 3 kva power requirement is being supplied by 250 kva transformer?

The result is that the transformer runs cool and contented. The '250 KVA' rating on the transformer is its maximum ability to transfer power from its input to its output without overheating, NOT an amount of power always running through it. If the 3 KVA load happens to be the only thing connected to the transformer at the time, then only 3 KVA flows into the transformer from the primary line, and only 3 KVA leaves the transformer secondary.