if you have 200 kva so it's 160 KW then ,you need 400 A MCCB and setting at 0.9 and use cable 4c.185 mm2 if the SMDB is nearby and all this will be change according to the ambient temperature and the electrical code used in your area
A breaker is not sized by individual phase amperage. It will be a three phase or three pole breaker rated at the output of the generator. Use the following formula to find the output amperage of the three phase generator.
Amps = kva x 1000/1.73 x voltage.
The generator should be about ¾ hp.
From the nameplate on the welder you find the amperage that the welder draws at the three phase voltage that you are going to use. This amperage is used to size the phase converter. This amperage is also used to size the breaker that will feed the phase converter and wire size for the installation.
I=270000/380/1.732 I=410A USE: 500A CIRCUIT BREAKER
The first thing you have to do is find the full load amps of the motor. The wire size feeding the motor has to be 125% of the full load current. The breaker is usually 250% of the full load current. If the voltage and amperage had been added to the question the exact breaker size could have been calculated.
Add up your amps to calculate your breaker size. Add up your loads (amps), divide by 0.8, and choose that size breaker. If that number does not correspond to a standard size breaker you go to the next higher standard size breaker.
Depends on the wire size you are using. If the generator breaker is a 30 amp then install a 30 amp breaker.
The question isn't the number of amps total on your branch circuits, but rather, what your MAIN breaker(s) are rated at. This will determine what size of generator you will need. And be certain that the generator is 3-phase. <<>> The formula you are looking for is Amps = kva x 1000/1.73 x voltage.
If it is a portable generator the breaker should be self contained within the generators panel. If the generator is a stationary standby unit a voltage has to be stated to calculate the conductor size and hence the breaker size to protect the conductor. Amps = Watts/Volts.
50amp but if considering the breaker cannot withstand starting current you need to size the breaker up.
The generator should be about ¾ hp.
The job of a breaker is to limit the amount of current that is applied to the size of wire that is connected to the breaker.
10amp
From the nameplate on the welder you find the amperage that the welder draws at the three phase voltage that you are going to use. This amperage is used to size the phase converter. This amperage is also used to size the breaker that will feed the phase converter and wire size for the installation.
To answer this question a voltage must be given to find the current output. Also whether the generator is three phase or single phase.
The cable that is used to connect from the generator is based on the size in kW's of the generator and the generator's breaker size rated in amps. It usually is a flexible cab-tire 4 wire cable if the generator is a portable type. If it is a stationary generator is has to be wired with a flexible conduit so as not to transmit vibration from the generator to the conduit system.
As example, at 380V the generator produces 685A per phase. Therefore you will require 2 x 120mm2 cables per phase. (1 x 120mm2 cable will support 365A per phase). In total you will require approximately 1/2km of cable to cover the 50m run between the generator and the ATS panel/Load. i.e. 5 phases in total - 2 x 50m cables per phase.
The size of the generator is based on the size of the load you want to supply. Size up the load in watts or amps along with what phase (single or three) and voltage that the load requires. These are needed to give a complete answer.