Q: How many breakers on transformer in one?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Will REF protect the outgoing cables when the Ct's are fitted at the transformer?

REF protection, when installed and set correctly, will protect everything within the CT's. If the CTs are on breakers, then yes, the cables from the transformer to the breakers will be in the zone of protection. If the CTs used are in the bushings of the transformer, then no.


Why are large transformers designed not to have optimum regulation in order for circuit breakers to be within reasonable size?

Transformer voltage regulation and size of the circuit breakers have no direct relation


What is use of bushing in transformer?

A bushing is a hollow insulator, used with transformers and circuit breakers. It provides a means by which an energised conductor can pass from the outside to the inside of the transformer or circuit breaker.


How you using ref relay in transformer?

an REF relay (restricted earth fault) is used to provide ground fault protection for a transformer. Its' operation is limited by CTs starred towards the transformer (usually on the transformer bushings or in breakers used to isolate the transformer), so it will only operate for transformer related faults. Because of this, it can be set to operate very quickly.


Where are bonk breakers available?

There are many online shops that sell bonk breakers. Amazon.com is one of online shop that sells bonk breakers with any kind of models. You can visit www.amazon.com


How many type of transformer?

one or two i think


Which device gives protection against the internal faults occurring in a transformer?

Supply transformers at substations are provided with circuit-breakers for protection.


What is the effect of back charging of 250MVA 15.75KV 240KV generator transformer and how many times one can back charge the generator transformer?

Generator Transformer back-charging is done because of the following reasons:- 1. To ensure the healthiness of Generator transformer after performing all the transformer related tests before synchronising with the grid. 2. To ensure all the protections of transformer before putting it into actual operation. 3. To check the polarity, ratio & connections of transformer. 4. To check all the PTs & CTs in circuit & their availability to the relays for protection & metering. 5. To check Voltage level & polarity at LAPT. 6. To perform change-over operation checks of UATs & the tie breakers with main breakers. Since all the protection system related to relays acts in the same way for forward & reverse power, we check the availabilty of each equipment before final synchronisation with the grid.


How many 12V 50W bulbs can you run on a 20-60VA transformer?

A 60VA transformer can run only one 50W bulb.


How many houses can be run off of one electrical transformer drum?

Depends on the rating of the transformer and the running load of the houses connected to it.


A transformer can only?

A transformer does many things.


Where can one purchase Cutler Hammer circuit breakers?

Cutler Hammer circuit breakers can be purchased at many retailers that specialize in electronics. Some of these retailers include Relectric, Automation Direct, Best Circuit Breakers, Home Depot and Amazon.